IM 04P01B01-01E 
2-8
2.4  Optional Terminal Wiring
General Precautions to be Taken While Wiring the Input/Output Signal Wires
  WARNING
•  To prevent electric shock while wiring, ensure that the power supply source is 
turned OFF.
•  If a voltage of more than 30 VAC or 60 VDC is to be applied to
 the output 
terminals, use ring-tongue crimp-on lugs with insulation sleeves on all terminals 
to prevent the wires from slipping out when the screws become loose. 
Furthermore, use double-insulated wires (dielectric strength of 2300 VAC or 
more) for the signal wires on which a voltage of more than 30 VAC or 60 VDC is 
to be applied. For all other wires, use basic insulated wires (dielectric strength of 
1390 VAC). To prevent electric shock, attach the terminal cover after wiring and 
make sure not to touch the terminals.
Crimp-on lug with insulation sleeves (for 4-mm screws)
  CAUTION
•  The option terminals of this instrument are specific to this instrument. Do 
not connect the option terminals of the µR1000, µR1800 or other models, as 
malfunction may result.
•
  To prevent fire, use signal wires having a temperature rating o
f 70°C or more.
•  If a strong tension is applied to the cable wired to the recorder, the terminals of 
the recorder and/or the cable can be damaged. In order to prevent tension from 
being applied directly on the terminals, fasten all wiring cables to the rear of the 
mounting panel.
Arrangement of the Optional Terminals
As shown in the figure below, the optional terminal block is located on the rear panel.
The optional terminal block is provided on the recorder when an option that requires 
input/output is installed such as the alarm output relay (/A1, /A2, or /A3 option), FAIL/
chart end output (/F1 option), remote control function (/R1 option), RS-422A/485 
interface (/C3 option)
*
, and Ethernet (10BASE-T) interface (/C7 option)
*
. A terminal cover 
is screwed in place on the measuring input terminal block. A label indicating the terminal 
arrangement is affixed to the terminal block.
*  For details on terminal and connector arrangement and wiring, see the µR10000 /µR20000 
Communication Interface User’s Manual (IM 04P01B01-17E).
Optional terminal block
Terminal cover 
attachment screws