User Manual
4-14
IM 04P01B01-17E
4.4 Setting Commands
VR  Turns ON/OFF the recording on 
each channel.
Dot model
Syntax
  VR p1,p2,p3
<terminator>
p1 
Channel number
p2 
Trend recording ON/OFF (ON, OFF)
p3 
Periodic printout ON/OFF (ON, OFF)
Query
  VR[p1]?
Example  Turn trend recording ON and turn periodic 
printout OFF on channel 06.
VR06,ON,OFF
Description On models with the computation function (/M1 
option), computation channels can be specified.
Pen model
Syntax
  VR p1,p2
<terminator>
p1 
Channel number
p2 
Periodic printout ON/OFF (ON, OFF)
Query
  VR[p1]?
Example  Turn periodic printing ON on channel 01.
VR01,ON
Description
 On models with the computation function (/M1 
option), computation channels can be specified.
ST  Sets the tag.
Syntax
  ST p1,p2
<terminator>
p1
  Channel number
p2
  T
ag string (up to 7 characters)
Query
  ST[p1]?
Example
  Set the tag of channel 02 to 
TI-2.
ST02,TI-2
Description
 •
  For the characters that can be used for the 
tags, see appendix 1, “ASCII Character 
Codes.”
•
  On models with the computation function 
(/M1 option), computation channels can be 
specified.
SG  Sets the message.
Syntax
  SG p1,p2
<terminator>
p1
  Message number (1 to 5)
p2
  Message string (up to 16 characters)
Query
  SG[p1]?
Example
  Set character string “START” in message 
number 1.
SG1,START
Description
 For the characters that can be used for the 
messages, see appendix 1, “ASCII Character 
Codes.” 
SE  Sets the secondary chart speed 
(used by the remote control 
function (/R1 option)).
Syntax
  SE p1
<terminator>
p1 
Secondary chart speed
  See the explanation.
Query
  SE?
Example  Set the chart speed to 50 mm/h.
SE50
Description
 Select the chart speed from the list of choices 
below
.
Pen model
5 to 12000 mm/h (82 levels, see section 4.3)
Dot model
1 to 1500 mm/h (1 mm steps)
SV  Sets the moving average 
(dot model).
Syntax
  SV p1,p2
<terminator>
p1 
Channel number
p2 
Number of samples for computing the 
moving average (OFF, 2 to 16) [times]
Query
  SV[p1]?
Example  Set the number of samples for computing the 
moving average of channel 02 to 12.
SV02,12
Description
 •
  This setting is available on the dot model.
•
  This setting is possible when moving average 
is enabled (UI command).
SF  Sets the input filter (pen model).
Syntax
  SF p1,p2
<terminator>
p1 
Channel number
p2 
Filter time constant (OFF, 2s, 5s, 10s)
Query
  SF[p1]?
Example  Set the filter of channel 02 to 2 s.
SF02,2s
Description
 This setting is possible when the input filter is 
enabled (UJ command).
BD  Sets the alarm delay time.
Syntax
  BD p1,p2
<terminator>
p1 
Channel number
p2 
Alarm delay (1 to 3600) [s]
Query
  BD[p1]?
Example  Set the alarm delay of channel 01 to 120 s.
BD01,120
Description
 •
  This setting is possible when the alarm delay 
function is enabled (UF command).
•
  On models with the computation function 
(/M1 option), computation channels can be 
specified.
VF  Sets the brightness of the display 
(VFD) and internal illumination.
Syntax
  VF p1,p2
<terminator>
p1 
VFD brightness (1 to 8)
p2 
Internal illumination (OFF, 1 to 4)
OFF
  T
urns OFF the internal 
illumination.
Query
  VF?