User Manual
53
IM 04P01B01-02E 
Setup Items in Basic Setting Mode and Their Default Values 
(Recorder version: 1.31)
Setup Item Pen/Dot Selectable Range or Selections Default Value
Alarm > Diagnosis - On/Off Off
Alarm > Reflash - On/Off Off
Alarm > AND - None/I01/I01-I02/I01-I03/I01-I04/I01-I05/I01-I06 None
Alarm > Act - Energize/De_energize Energize
Alarm > Behavior - Nonhold/Hold Nonhold
Alarm > Indicator - Nonhold/Hold Nonhold
Alarm > Increase - 01 to 15 01
Alarm > Decrease - 01 to 15 01
Alarm > Hysteresis - Off/0.1% to 1.0% 0.5%
Alarm > M_Hysteresis - Off/0.1% to 1.0% Off
A/D > Integrate Dot Model Auto/50Hz/60Hz/100ms Auto 
Pen Model Auto/50Hz/60Hz Auto
Burnout > CH - 01 to 06 01
Burnout > Burnout - Off/Up/Down Off
RJC > CH - 01 to 06 01
RJC > RJC - Internal/External Internal
RJC > RJC > Volt - –20000 to 20000 µV 0 µV
Color > Channel Dot Model 01 to 06 01
Color > Color Dot Model Purple/Red/Green/Blue/Brown/Black
01: Purple, 02: Red, 
03: Green, 04: Blue, 
05: Brown, 06: Black
POC > POC Pen Model On/Off Off
Print > CH/Tag - CH/Tag CH
Print > Channel Dot Model On/Off On
Print > Alarm - On1/On2/Off On1
Print > Record On - On/Off Off
Print > Chart speed - On/Off On
Print > Scale - On/Off On
Print > Pen color Pen Model On/Off On
Print1 > Periodic - Auto/Manual Auto
Print1 > Ref. Time - Hour 0 to 23 (1 hour steps) 00:00
Print1 > Interval - 10min/15min/20min/30min/1h/2h/3h/4h/6h/8h/
12h/24h
1h
Print1 > Mode - Inst/Report/Off Inst
Print2 > CH - 01 to 06 01
Print2 > Mode - AVE/MIX/SUM/MIN/MAX/INST AVE
Print2 > SUM scale - Off, /s, /min, /h, /day Off
Bar graph > CH - 01 to 06 01
Bar graph > Graph - Normal/Center Normal
Keylock > Keylock - Not/Use Not
Keylock > Password - Numbers and spaces within 4 digits Blank
Keylock > RCD - Free/Lock Free
Keylock > Feed - Free/Lock Free
Keylock > Menu - Free/Lock Free
Keylock > Disp Menu - Free/Lock Free
Keylock > Alarm ACK - Free/Lock Free
Keylock > Math - Free/Lock Free
Keylock > Print out - Free/Lock Free
Keylock > Message - Free/Lock Free
Keylock > Buffer clear - Free/Lock Free
Keylock > Periodic - Free/Lock Free
Keylock > Pen exchange Pen Model Free/Lock Free
Keylock > R. exchange Dot Model Free/Lock Free
Moving_AVE > Moving_AVE Dot Model Not/Use Not
Filter > Filter Pen Model Not/Use Not
Partial > Partial - Not/Use Not
Language > Lang - English/Japanese/German/French English
Date format > Type - Y/M/D M/D/Y D/M/Y D.M.Y M.D.Y M.D.Y
Temperature > Temp - °C/°F °C
Setup Items and Default Values