User Manual
37
IM 04P01B01-02E 
Selecting the Input Type
5.
  Press the   key to select Scale, and press the   key (for the selectable 
settings, see “Explanation” on page 38).
Mode=Scale
Scales and record
6.
  Press the   key to select Volt and then press the   key.
Type=Volt
DC Voltage
7.
  Press the   key to select 20V and then press the   key.
Range=20V
20mV-50V
Setting Span Left
8.
  Set Span_L to 0.00, and press the   key.
Press the 
 key to select the desired digit. Press the   key to select the 
value.
Span_L= 0.00
 -20.00/ 20.00V
Displays the range of Span_L.
Setting Span Right
9.
  Likewise, set Span_R to 10.00, and press the   key.
Span_R= 10.00
 -20.00/ 20.00V
Displays the range of Span_R.
Setting the Decimal Position and Scale Left
10.
 Display Scale_L.
Scale_L= 0.00
-200.00/ 300.00
Displays the scaling range.
11.
  Press the   key to select the desired digit.
Scale_L= 0.00
-200.00/ 300.00
12.
 Press the   key to select space and then press the   key (Scale_L is set to 0.0).
Scale_L= 0.0
-200.00/ 300.00
Setting Scale Right
13.
 Likewise, set Scale_R to 400.0, and press the   key.
Scale_R= 400.0
-2000.0/ 3000.0
The Setting complete screen is displayed. When this screen is displayed, the 
settings entered up to then are applied.
Finishing the Settings
14.
 When the Setting complete screen is displayed, press the ESC key.
The Set=Range screen is displayed.
04-04 Channel
Setting complete
Set=Range
Input range and
Setting the Unit and Finishing the Unit Settings
See steps 13 to 17 in Setup Example (2).
15.
 Hold down the 
MENU
 key for 3 seconds to return to Operation mode.
*  When the key or key is pressed while holding down the SHIFT key, the operation is reversed as 
  when the respective key is pressed by itself.
Setting the Input Range and Alarm on Measurement Channels