User Manual
34
IM 04P01B01-02E 
Setting Span Right
8.
  Likewise, set Span_R to 450.0 and press the   key.
Span_R= 450.0
-200.0/ 1370.0°C
The Setting complete screen is displayed. When this screen is displayed, the 
settings entered up to then are applied.
Finishing the Settings
9.
  When Setting complete screen is displayed, do either of the following:
Press the 
 key to set other channels.
To nish setting the input range, press the ESC key.
02-02 Channel
Setting complete
10.
 Hold down the 
MENU
 key for 3 seconds to return to Operation mode.
Setup Example (2) of 1-5V Input and unit
Set channel 03 to 1 to 5V standard signal input and 0.0 to 500.0% scale. The scaling 
range is –20000 to 30000. The scaling range is –20000 to 30000 excluding the decimal 
point.
The measured values in the range of 0.0 to 500.0% are recorded in a width of 100 mm 
on the chart paper.
1V 5V
1-5V standard signal
0.0% 500.0%
(Scale left) (Scale right)
1.000 5.000
(Span left) (Span right)
Chart paper
100 mm
Entering Setting Mode
1.
  Hold down the 
MENU
 key for 3 seconds to enter Setting mode.
Selecting the Range
2.
  Press the   key with Range shown on the screen.
Set=Range
Input range and
Displays a description of the setup item.
Selecting the Channel Range
3.
  Press the   key to set the first channel to 03 and then press the   key.
First channel
Last channel
CH=03-03
First channel 01-
Displays the selectable range of channels.
4.
  Likewise, set the last channel to 03 and then press the   key.
*  When the key, key, or CHARACTER key is pressed while holding down the SHIFT key, the 
  operation is reversed as when the respective key is pressed by itself.
Setting the Input Range and Alarm on Measurement Channels