User Manual
19
IM 04P01B01-02E 
Power Supply Wiring
  WARNING
Panel Mount Type
•  To prevent electric shock when wiring, ensure the main power supply is turned 
OFF.
•  To prevent the possibility of fire, use 600 V PVC insulated wire
 (AWG20 to 16) or 
an equivalent wire for power wiring.
•  Make sure to earth ground the protective earth terminal through a grounding 
resistance less than 100 Ω before turning ON the power
.
•  Use crimp-on lugs (designed for 4-mm screws) for power and ground wiring 
termination.
•  To prevent electric shock, make sure to close the transparent 
cover for the 
power supply wires.
•  Make 
sure to provide a power switch (double-pole type) on the power supply line 
in order to separate the recorder from the main power supply. Put an indication 
on this switch as the breaker on the power supply line for the recorder and 
indications of ON and OFF.
  Switch specifications
  Rated power current: 1 
A or more (other than /P1), 3 
A or more (/P1 option)
  Rated rush current: 60 A or more (other than /P1), 70 A or more (/P1 option) 
Complies with IEC 60947-1, 3.
•  Connect a fuse in the power supply line.
  2 A
 to 15 A (other than /P1), 4 A to 15 A (/P1 option)
•  Do not add a switch or fuse to the ground line.
Portable Type (/H5x Option)
•  Ensure that the source voltage matches the rated power supply voltage of the 
instrument before connecting the power cord.
•  Connect 
the power cord after checking that the power switch of the portable type 
is turned OFF.
•  To prevent electric shock or fire, be sure to use the power cord
 for the portable 
type supplied by YOKOGAWA.
•  Make sure to connect protective earth grounding to prevent electric shock. 
Connect the power cord of the portable type to a three-prong power outlet 
equipped with a protective earth terminal.
•  Do not use an extension cord that does not have a protective grounding wire. 
The protective features of the instrument will be rendered inef
fective.
Use a power supply that meets the following conditions:
Item Power Supply Specifications
(Options Other Than /P1) (/P1 Option)
Rated supply voltage 100 to 240 VAC 24V DC/AC
Allowable power supply voltage range 90 to 132/180 to 264 VAC 21.6 V to 26.4 VDC/AC
Rated power supply frequency 50/60 Hz 50/60 Hz (for AC)
Allowable power supply frequency range 50/60 Hz ±2% 50/60 Hz ±2% (for AC)
Maximum power consumption 40 VA 25 VA (for DC) or 35 VA (for AC)
Note
Do not use a supply voltage in the range 132 to 180 VAC, as this may have adverse effects on 
the measurement accuracy.
Installing/Wiring the Recorder