Energy Meter Manual

<Toc> <Ind> <5. Modbus/RTU and ASCII Communication Protocols>
5-15
IM 77C01E01-10E
Example (ASCII mode)
Write 10 into a series of four D registers starting with the D0201 (VT ratio and CT ratio) at
station number 11.
[Message] [:]0B1000C800004120000041204F[CR][LF]
0B: station number 11, 10: function code 16, 00C8: D register start number 201,
0004: number of D registers 4, 08: byte count (number of D registers × 2), 0000: VT
ratio lower two bytes, 4120: VT ratio upper two bytes, 0000: CT ratio lower two bytes,
4120: CT ratio upper two bytes and 4F: error check
* Numbers in quotation marks are hexadecimal.
The following response will be returned to the message above.
[Response]
[:]0B1000C8000419[CR][LF]
Write 1 into the D0207(setup change status) to activate the writing into the VT ratio and CT
ratio.
[:]0B0600CE000120[CR][LF]
0B: station number 11, 06: function code 06, 00CE: D register start number 207,
0001: writing data 0001, and 20: error check
* Numbers in quotation marks are hexadecimal.