Energy Meter Manual

5-14
<Toc> <Ind> <5. Modbus/RTU and ASCII Communication Protocols>
IM 77C01E01-10E
16 Writes data into multiple D registers
Function
This function code writes data into successive D registers by the number starting with a
specified D registers number.
The maximum number of D registers to be written into at a time is 32.
For the format of response in the event of failure, see subsection 5.1.4.
Broadcast addressing is possible (by setting 00 to the station number).
No response is returned when using the broadcast addressing.
Message (for normal operation)
End of Message
Mark
(CR + LF)
None
2
Byte
Count
1
2
Data
(Upper Digit)
1
2
Data
(Lower Digit)
1
2
Error
Check
2
2
Number of
D Registers
(Upper Digit)
1
22
1
Number of
D Registers
(Lower Digit)
Massage (continued)
Element
Number of bytes
in RTU mode
Number of bytes
in ASCII mode
Start of
Message
Mark (:)
None
1
Station
Number
(ST-NO)
1
2
Function Code
(10)
1
2
D-Register Start
Number
(Upper Digit)
1
22
1
D-Register Start
Number
(Lower Digit)
Response (for normal operation)
Element
Number of bytes
in RTU mode
Number of bytes
in ASCII mode
Start of
Message
Mark (:)
None
1
Number of
D Registers
(Lower Digit)
1
2
Number of
D Registers
(Upper Digit)
1
2
Error
Check
2
2
Station
Number
(ST-NO)
1
2
None
End of Message
Mark
(CR + LF)
2
Function
Code
(10)
1
2
D-Register
Start Number
(Upper Digit)
1
22
1
D-Register
Start Number
(Lower Digit)
Response (continued)