Energy Meter Manual

<Toc> <Ind> <5. Modbus/RTU and ASCII Communication Protocols>
5-13
IM 77C01E01-10E
08 Performs loop back test
Function
This function code is used to check connection for communication.
For the format of response in the event of failure, see subsection 5.1.4.
The 00 shown below (marked with an asterisk *) are fixed.
Any value can be selected for transmit data.
Message (for normal operation)
Element
Number of bytes
in RTU mode
Number of bytes
in ASCII mode
Start of
Message
Mark (:)
None
1
Error
Check
2
2
Station
Number
(ST-NO)
1
2
None
End of Message Mark
(CR + LF)
2
Function Code
(08)
1
2
00
0000
2
44
2
Transmit Data
(Arbitrary)
Message (continued)
Response (for normal operation)
Element
Number of bytes
in RTU mode
Number of bytes
in ASCII mode
Start of
Message
Mark (:)
None
1
Error
Check
2
2
Station
Number
(ST-NO)
1
2
None
End of Message Mark
(CR + LF)
2
Function Code
(08)
1
2
00
0000
2
44
2
Same as
Transmit Data
Response (continued)
Diagnostic Codes
Meaning
Command message return
Diagnostic Code
0000
Data
Arbitrary
Example (ASCII mode)
Send data 0000 (fixed) and transmit data 04D2 (arbitrary) to the station number 11 to check
the connection for communication.
[Message] [:]0B08000004D217[CR][LF]
When the connection is normal, the following response same as the command will be
returned.
[Response] [:]0B08000004D217[CR][LF]