06 Writes data into D register
Function
This function code writes data into a specified D registers number.
The maximum number of D registers to be written into at a time is 1.
For the format of response in the event of failure, see subsection 5.1.4.
Broadcast addressing is possible (by setting 00 to the station number).
Message (for normal operation)
Element
Number of bytes
in RTU mode
Number of bytes
in ASCII mode
1
Write Data
(Upper Digit)
2
Start of
Message
Mark (:)
None
1
Write Data
(Lower Digit)
1
2
Error
Check
2
2
Station
Number
(ST-NO)
1
2
None
End of Message Mark
(CR + LF)
2
Function Code
(06)
1
2
D-Register
Number
(Upper Digit)
1
22
1
D-Register
Number
(Lower Digit)
Message (continued)
Response (for normal operation)
Element
Number of bytes
in RTU mode
Number of bytes
in ASCII mode
1
Write Data
(Upper Digit)
2
Start of
Message
Mark (:)
None
1
Write Data
(Lower Digit)
1
2
Error
Check
2
2
Station
Number
(ST-NO)
1
2
None
End of Message Mark
(CR + LF)
2
Function Code
(06)
1
2
D-Register
Number
(Upper Digit)
1
22
1
D-Register
Number
(Lower Digit)
Response (continued)
Example (ASCII mode)
Write 0001 into the D0302 (optional integration start/stop) at station number 11.
[Message] [:]0B06012D0001C0[CR][LF]
0B: station number 11, 06: function code 06, 012D: D register number 302, 0001:
data 0001, and C0: error check
* Numbers in quotation marks are hexadecimal.
The following response will be returned to the message above.
[Response] [:]0B06012D0001C0[CR][LF]
The frame same as the message is returned.