Energy Meter Manual

<Toc> <Ind> <2. Setup>
2-11
IM 77C01E01-10E
Setting for PR300 to perform the Ethernet-serial gateway function
To use the Ethernet-serial gateway function, set the parameters of subsection 2.2.2, Con-
ditions for Ethernet Communication and set a parity (PRI) in Table 2.3.
When the protocol is set to Modbus/TCP, the parameters of RS-485 other than the parity
are fixed and unchangeable.
Table 2.3 Parameters of PR300 to Perform the Ethernet-Serial Gateway Function
(ST-NO)
(RS-485
communication)
(B-RT)
(PRI)
(STP)
(DLN)
01 (fixed)
9600
NONE
1
8
1 (fixed)
8 (fixed)
01
9600 bps (fixed)
NONE
EVEN
ODD
Parameter Name
Parameter Symbol
Menu Setting Range
Initial
Value
Baud rate
Data length
Station number
None
Even
Odd
Parity
Stop bit
Slave PR300
The station number of any slave PR300 (device for RS-485 communication) must be a
different number other than 01.
The communication conditions for any slave PR300 (device for RS-485 communication)
other than the station number must conform to those in Table 2.3.
Table 2.4 Parameters of Slave PR300
(ST-NO)
(RS-485
communication)
(B-RT)
(PRI)
(STP)
(DLN)
2400 bps
9600 bps
19200 bps
1
2
7
8
NONE
EVEN
ODD
02 to 99
9600
NONE
1
8
01
Parameter Name
Parameter Symbol
Menu Setting Range
Initial
Value
Baud rate
Data length
Station number
None
Even
Odd
Parity
Stop bit
When using the VJET Ethernet/RS-485 converter as an Ethernet-serial gateway function,
the communication conditions of any slave PR300 must conform to those of the VJET at a
higher level. The initial value of the VJET parity is EVEN.