• Example
Reads in batch the measured values and maximum/minimum value of PR300 with station
number 01.
[Command]
[STX]DGA01䊐䊐[ETX][CR]
Returns the following response for the above command.
[Response]
[STX]DGA01100001000010000+1.000E+31.000E+31.000E+3G0.8001.000E+31.000E+21.000E+3䊐䊐[ETX][CR]
(1) (2) (3) (4) (5) (6) (7) (8) (9) (10)
(1) Active energy: 10000 kWh, (2) Optional electric energy (previous value):
10000 Wh, (3) Optional electric energy (current value): 10000 Wh, (4) Active
power: +1.000E+3 W (1000 W), (5) Voltage-1: 1.000E+3 V (1000 V),
(6) Current-1: 1.000E+3 A (1000 A), (7) Power factor: G0.800,
(8) Maximum voltage-1: 1.000E+3 V (1000 V), (9) Minimum voltage-1:
1.000E+2 V (100 V), (10) Maximum current-1: 1.000E+3 A (1000 A)
● Parameter: B (Reads maximum voltage-1), Parameter: C (Reads minimum
voltage-1), Parameter: N (Reads maximum voltage-2), Parameter: P (Reads
maximum voltage-3), Parameter: Q (Reads minimum voltage-2), Parameter: R
(Reads minimum voltage-3)
• Function
Reads the maximum voltage-1 by parameter: B, the minimum voltage-1 by parameter C,
the maximum voltage-2 by parameter: N, the maximum voltage-3 by parameter: P, the
minimum voltage-2 by parameter: Q, and the minimum voltage-3 by parameter: R.
• Command/response
Number
of bytes
121 2
2
11
Command
element
STX DG B
(C)
(N)
(P)
(Q)
(R)
Station
number
(ADR)
Checksum
ETX CR
There is no command data for data reading.
121 2 8
Response
element
STX DG B
(C)
(N)
(P)
(Q)
(R)
Station
number
(ADR)
ⵧ.ⵧⵧⵧE䊊
211
Checksum ETX CR
Number
of bytes
Response data is returned as an 8-byte ASCII character string (0.000E+0 to 9.999E+6).