Energy Meter Manual

8-10
<Toc> <Ind> <8. PR201 Original Communication Protocol>
IM 77C01E01-10E
Example
Reads a power factor of PR300 with station number 01. 䊐䊐 indicates the checksum value.
[Command]
[STX]DG601䊐䊐[ETX][CR]
Returns a response of power factor G0.8 for the above command.
[Response]
[STX]DG601G0.800䊐䊐[ETX][CR]
Parameter: 7 (Starts optional integration)
Function
Starts optional integration.
Command/response
Number
of bytes
121 2
2
11
Command
element
STX DG 7
Station
number
(ADR)
Checksum
ETX CR
There is no command data for data reading.
121 2 0
Response
element
STX DG 7 Station
number
(ADR)
No data
211
Checksum ETX CR
Number
of bytes
There is no response data.
Example
Starts optional integration of PR300 with station number 01. 䊐䊐 indicates the checksum
value.
[Command]
[STX]DG701䊐䊐[ETX][CR]
Returns the following response for the above command.
[Response]
[STX]DG701䊐䊐[ETX][CR]