Energy Meter Manual
<Toc> <Ind> <7. Functions and Usage of D Registers>
7-5
IM 77C01E01-10E
D-Reg
Ref No. H No. Register Symbol Register Name Effective Range
Initial Value
BackUp R/W
No.
D0289 40289 0120
DEFAULT GATEWAY 1
Default gateway-1 (uint 32, 1 byte) 0 to 255 0
䊊
R/W
D0290 40290 0121
DEFAULT GATEWAY 2
Default gateway-2 (uint 32, 1 byte) 0 to 255 0
䊊
R/W
D0291 40291 0122
DEFAULT GATEWAY 3
Default gateway-3 (uint 32, 1 byte) 0 to 255 0
䊊
R/W
D0292 40292 0123
DEFAULT GATEWAY 4
Default gateway-4 (uint 32, 1 byte) 0 to 255 0
䊊
R/W
D0293 40293 0124 PORT NUM Port number 502, 1024 to 65535 502
䊊
R/W
If other than 1: Invalid
D0294 40294 0125 ETHERNET STS Ethernet writing status If 1: Writing is executed
–
W
(D0281 to D0293 are validated)
D0295 to D0300
D0301 40301 012C
INTEG START STOP
Integration start/stop 0: Stop, 1: Start 1
䊊
R/W
D0302 40302 012D Wh START STOP Optional integration start/stop 0: Stop, 1: Start 0
R/W
D0303 to D0310
D0311 40311 0136
DEMAND START STOP
Demand measurement start/stop 0: Stop, 1: Start 0
R/W
Confirmation and release of
0: Normal state, 1: Alarm state
D0312 40312 0137
DEMAND ALM STATUS
demand alarm state
Writing “0” during alarm state clears 0
R/W
the alarm.
D0313 to D0350
If other than 1: Invalid
D0351 40351 015E MAX RST Maximum/minimum values reset If 1: Maximum/minimum values
–
W
are reset (D0101 to D0138)
If other than 1: Invalid
D0352 40352 015F Wh ALL RST Energy value all-reset If 1: All energy values are reset
–
W
(D0001 to D0010)
If other than 1: Invalid
D0353 40353 0160 kWh RST Active energy reset If 1: Active energy is reset
–
W
(D0001, D0002)
If other than 1: Invalid
D0354 40354 0161 RkWh RST Regenerative energy reset If 1: Regenerative energy is reset
–
W
(D0003, D0004)
If other than 1: Invalid
D0355 40355 0162 kVarh RST Reactive energy reset If 1: Reactive energy is reset
–
W
(D0005 to D0008)
If other than 1: Invalid
D0356 40356 0163 kVAh RST Apparent energy reset If 1: Apparent energy is reset
–
W
(D0009, D0010)
D0357 to D0370
D0371 40371 0172 kWh SET L
Active energy – setpoint (uint 32, lower 2 bytes)
See subsection 3.6.1
–
W
D0372 40372 0173 kWh SET H
Active energy – setpoint (uint 32, upper 2 bytes
)
If other than 1: Invalid
D0373 40373 0174 kWh STS Active energy writing status If 1: The values of D0371 and D0372
–
W
are written as the integrated values.
D0374 40374 0175 RkWh L
Regenerative energy – setpoint
(uint 32, lower 2 bytes)
See subsection 3.6.2
–
W
D0375 40375 0176 RkWh H
Regenerative energy – setpoint
(uint 32, upper 2 bytes)
If other than 1: Invalid
D0376 40376 0177 RkWh STS Regenerative energy writing status If 1: The values of D0374 and D0375
–
W
are written as the integrated values.
D0377 40377 0178
Lead kVarh SET L
LEAD reactive energy – setpoint
(uint 32, lower 2 bytes)
See subsection 3.6.3
–
W
D0378 40378 0179
Lead kVarh SET H
LEAD reactive energy – setpoint
(uint 32, upper 2 bytes)
D0379 40379 017A
Lag kVarh SET L
LAG reactive energy – setpoint
(uint 32, lower 2 bytes)
See subsection 3.6.4
–
W
D0380 40380 017B
Lag kVarh SET H
LAG reactive energy – setpoint
(uint 32, upper 2 bytes)
If other than 1: Invalid
D0381 40381 017C kVarh STS Reactive energy writing status If 1: The values of D0377 to D0380
–
W
are written as the integrated values.
D0382 40382 017D kVAh SET L Apparent energy – setpoint
(uint 32, lower 2 bytes)
See subsection 3.6.5
–
W
D0383 40383 017E kVAh SET H Apparent energy – setpoint
(uint 32, upper 2 bytes)
If other than 1: Invalid
D0384 40384 017F kVAh STS Apparent energy writing status If 1: The values of D0382 and D0383
–
W
are written as the integrated values.
D0385 to D0399
If other than 1: Invalid
D0400 40400 018F RMT RST Remote reset If 1: PR300 is reset (the same effect 0
W
as turning the power off and then on)
* D register with a blank cannot be used. (Writing to this area is not guaranteed.)