Energy Meter Manual

<Toc> <Ind> < 6. Modbus/TCP Communication Protocol>
6-9
IM 77C01E01-10E
16 Writes data into multiple D registers
Function
This function code writes data into successive D registers by the number starting with a
specified D registers number.
The maximum number of D registers to be written into at a time is 32.
For the format of response in the event of failure, see subsection 6.4.4.
Broadcast addressing is possible (by setting 00 to the station number).
No response is returned when using the broadcast addressing.
Request (for nomal operation): Writing data to n registers
12 2
2n
Data 1
Data n
Element
Number of bytes
Command
element
MBAP Header
22 2 2211
Hex value
Arbitrary 0000 2n+7 n
01 to 99
10
PDU
PDU
Unit ID
Function
code
Transaction ID
Protocol ID
Register
start number
Number of
registers
Number of
bytes
Byte
count
Request (continued)
● ● ● ●
Response (for normal operation)
01 to 99
Element
Number of bytes
Command
element
MBAP Header
22 2 2211
Hex value
Arbitrary 0000 0006 10 n
PDU
Unit ID
Function
code
Transaction ID
Protocol ID
Register
start number
Number of
registers
Number of
bytes