Energy Meter Instruction Manual

2
IM 77C01E01-02E 3rd Edition June 20, 2008
1.1.3 Mounting Method
Panel-mounting bracket
(standard accessory)
Bezel (standard accessory)
PR300
Panel-mounting bolt
(standard accessory: 2 bolts)
Bracket-fixing screw
(standard accessory: 2 screws)
Set the direction of the panel-mounting bracket.
2
2
1
3
3
Insert two panel-mounting bolts into the front of the panel-mounting bracket as
shown in the diagram.
2
Fix the panel-mounting bracket securely to the back of the PR300 with two
bracket-fixing screws as shown in the diagram.
3
Attach the bezel from the front of the PR300.
4
4
Insert the PR300 from its rear
through the mounting cutout in the
panel as shown in the diagram.
5
Secure the PR300s panel-mounting bolts by tightening them with the washers and nuts.
6
Front of the bracket
ANSI JIS
Front of the bracket
Rotate 90
Panel-mounting bolt
Flat washer, spring washer, and nut
(standard accessory: 2 of each)
5
6
6
The diagram below shows the front of the bracket (the side into which the
panel-mounting bolt is inserted). Rotating the bracket 90 makes the bracket
compatible with either ANSI or JIS panel cutouts. Set the bracket to either
the ANSI or JIS mark according to which type of panel you are installing, as
shown in the diagram.
(recommended tightening torque: 0.4 Nm)
(recommended tightening torque: 2.0 Nm)
1.2
Installation with the DIN 96-square Instrument Size
1.2.1 External Dimensions
Terminal cover
Dust cover
Mounting bracket
(2 places)
109
12.3
112.2
(124.5) (109)
96
110
96
1 to 10
(Acceptable panel thickness for mounting)
Unit: mm
1.5
1.2.2 Panel Cutout Dimensions
92
92
+0.8
0
+0.8
0
(68)
160 min.
Unit: mm
160 min.
(68)
Normal Allowable Deviation=±(Value of JIS B 0401-1998 tolerance grade IT18) / 2
1.2.3 Mounting Method
Mounting bracket
(standard accessory: 2 brackets)
2
2
Insert the PR300 from its rear through the
mounting cutout in the panel as shown in
the diagram.
1
1
Affix the mounting brackets to the left and
right sides of the PR300. Secure the
brackets to the PR300 by tightening the
screws in the end of the mounting brackets
with a screwdriver as shown in the
diagram.
2
(recommended tightening torque: 0.4 Nm)
2. Wiring
2.1 Single-phase two-wire system
11
12
13
14
15
16
17
18
19
20
21
22
c
d
1
3
5
7
9
10
6
b
a
e
23
24
25
f
2
4
8
L
N
PE
Power supply
Power-source
side
12
K
L
CT
Load side
Fuse
k
l
VT
U
V
1L
1S
P1
P2
u
v
Power supply voltage
100-240V AC±10% or
130-300V DC±15%
Refer to
“Other Wiring”
NOTE
Do not ground the input
circuit when connecting
voltage and current directly
without using VT and CT.
2.2 Single-phase three-wire system
11
12
13
14
15
16
17
18
19
20
21
22
2
4
6
8
9
10
7
1
3
5
23
24
25
u
u
v
v
1N2
K
L
CT
K
L
CT
VT
k
l
k
l
1L
1S
2L
2S
P0
P2
P1
U
U
V
V
L
N
PE
Fuse
Power supply
Power-source
side
Load side
Power supply voltage
100-240V AC±10% or
130-300V DC±15%
Refer to
Other Wiring
NOTE
Do not ground the input
circuit when connecting
voltage and current directly
without using VT and CT.
a
b
c
d
e
f
2.3 Three-phase three-wire system
11
12
13
14
15
16
17
18
19
20
21
22
2
4
6
8
1
3
5
7
9
10
23
24
25
123
K
L
CT
K
L
CT
VT
A
(R)
B
(S)
C
(T)
k
l
k
l
1L
1S
3L
3S
P1
P3
P2
U
U
V
V
u
u
v
v
L
N
PE
NOTE
Do not ground the input
circuit when connecting
voltage and current directly
without using VT and CT.
Power supply
Power supply voltage
100-240V AC±10% or
130-300V DC±15%
Refer to
Other Wiring
Power-source
side
Load side
Fuse
a
b
c
d
e
f
2.4 Three-phase four-wire system
11
12
13
14
15
16
17
18
19
20
21
22
1
23
45
6
7
8
9
10
23
24
25
N1
A
(R)
B
(S)
C
(T)
23
K
L
CT
K
L
CT
K
L
CT
VT
k
lk
l
k
l
1L
1S
2L
2S
3L
3S
P0
P1
P2
P3
U
U
V
u
u
U
u
v
V
v
V
v
L
N
PE
Power supply
Power-source
side
Load side
Fuse
Power supply voltage
100-240V AC±10% or
130-300V DC±15%
Refer to
Other Wiring
NOTE
Do not ground the input
circuit when connecting
voltage and current directly
without using VT and CT.
a
b
c
d
e
f
2.5 Three-phase four-wire system (2.5 element)
11
12
13
14
15
16
17
18
19
20
21
22
1
23
45
6
7
8
9
10
25
23
24
VT
U
U
V
V
Fuse
N1
A
(R)
B
(S)
C
(T)
23
K
L
CT
K
L
CT
K
L
CT
k
lk
l
k
l
1L
1S
2L
2S
3L
3S
P0
P1
P3
L
N
PE
Power supply
Power-source
side
Load side
Power supply voltage
100-240V AC±10% or
130-300V DC±15%
Refer to
Other Wiring
NOTE
Do not ground the input
circuit when connecting
voltage and current directly
without using VT and CT.
u
u
v
v
a
b
c
d
e
f
2.6 Other Wiring
1
23
45
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
a
b
c
d
e
f
Color
Description
Color
Description
Link LED
Off
Stopped
Active LED
Off
Stopped
Orange
10Mbps
Orange
Half duplex
Green
100Mbps
Green
Full duplex
Ethernet communication
10BASE-T
100BASE-TX
RJ45
connector
Pulse output
Contact capacity:
30V DC, 200mA
(resistive load)
Contact capacity:
30V DC, 200mA
(resistive load)
14
13
Analog output
Output signal:
4 to 20mA DC
12
11
+
+
Demand alarm output
ALM+
ALM
16
15
*1 If Ethernet communication is used, the RS-485
communication interface is used specifically for
the Ethernet-serial gateway function.
*2 In the case of the PR300 with the demand
measuring function, the demand alarm release
is selected.
Voltage signal
ON signal : 4.5 to 25V DC
OFF signal : within ±1V DC
RS-485 communication
A
R: 120(built-in)
TERM
B
SG
17
18
19
20
R
When terminating, short-circuit
terminals 17 and 18 with the
shorting bar
Optional integration
control signal or
demand alarm release
DI
DI
22
21
*1
*2
Switching between 10BASE-T and
100BASE-TX takes place automatically.
Switching between half and full duplex
takes place automatically.
3.
Attaching the Dust Cover and Terminal Cover
WARNING
As there is a danger of electric shock, do not attach the dust
cover and terminal cover while the wires are live.
Attach the dust cover before attaching the terminal cover.
The recommended tightening torque for the screws for attaching the
dust cover and terminal cover is 0.4Nm.
3.1 Attaching the Dust Cover
Dust cover
(standard accessory)
Insert into
the
marked
grooves
Insert the two protruding
portions on the underside of the
dust cover into the grooves on
the upper side of the PR300 as
shown in the diagram below.
1
Secure the dust cover with the screw
provided as shown in the diagram below.
2
(recommended tightening torque: 0.4 Nm)
3.2 Attaching the Terminal Cover
Complete the wiring to the terminals
2, 4, 6, 8, 23, 24, and 25, then
secure the terminal cover in the
open state shown in the diagram
below with the two screws provided.
1
Complete the wiring to other
terminals with the terminal
cover open shown in the
diagram below.
2
Close the terminal cover and secure it
with the screw provided as shown in
the diagram below.
3
(recommended tightening torque: 0.4 Nm)
(recommended tightening torque:
0.4 Nm)