User Manual

1-32
IM MX100-01E
Steady Output Operation
Output Operation While Communication Is Connected
Communication Connection Status Output Operation
Comm. connects (initial connection after power ON) Operation upon startup
Comm. connects Holds the output value (last output value)
(disconnected and restored for the 2nd or more time)
Communication disconnected normally Holds the output value (last output value)
Output Operation according to the Measurement Status and Transmission
Output Status
Transmission output in the table is ON when Transmission output is selected in the
Action menu of the MX100 Standard Software, or when DAQMXTRANSMIT_RUN is
executed in the MX100/DARWIN API. Transmission output in the table is OFF when
Transmission output is cleared in the Action menu of the MX100 Standard Software, or
when DAQMXTRANSMIT_STOP is executed in the MX100/DARWIN API.
Output Setting Status Output Operation
Trans. output Meas stop → meas. start Starts trans. output/holds within
within units units output value (depends on
trans. output execution on/off )
on: transmission output starts
off: holds output value
Measuring → meas. stop Holds output value
(last output value)
Meas stopping Trans. output exec. on* → off* Holds output val. (no change.)
Trans. output exec on → off Holds output val. (no change.)
Measuring Trans. output exec off → on Starts trans. output
Trans. output exec on → off Holds output val. (last val.)
Trans. output Meas stop → meas start Starts user output
or holds
between units output value (depends on trans
(user output) output exec. on/off status)
on: transmission output starts
of
f: output value held
Measuring → meas stop Holds output value
(last output value)
Meas stopping Trans. output exec off → on Holds output val. (no change.)
Trans. output exec on → off Holds output val. (no change.)
Measuring Trans. output exec off → on User output
Trans. output exec on → off
Holds output val. (last output value)
Manual output Meas stop → meas start No effect
(user output) Measuring → meas stop No effect
Meas stopping Trans. output exec off → on No effect
Trans. output exec on → off No effect
Measuring Trans. output exec off → on No effect
Trans. output exec on → off No effect
Pattern output Meas stop → meas start No effect
(user output) Measuring → meas stop No effect
Meas stopping Trans. output exec off → on No effect
Trans. output exec on → off No effect
Measuring Trans. output exec off → on No effect
Trans. output exec on → off No effect
* on: enabled off: disabled
Transmission output execute enabled: when “Transmit” under the Action menu of the PC
software is selected
Transmission output execute disabled: when “Transmit” under the Action menu of the PC
software is not selected
1.11 Operation of the 8-CH Medium-Speed Analog Output Module and the 8-CH Medium Speed PWM Output