General Precautions When Wiring the Signal Wires
WARNING
To prevent the possibility of electric shock when wiring, confirm that the
power supply source and the signal source are turned OFF. After making the
connections, secure the terminal cover and do not touch the terminals with your
hands.
For signal wires on which voltage exceeding 30 VAC/60 VDC is applied relative
to the ground potential or between signals, use reinforced (double) insulation
wires. For all other signal wires, use basic insulation wires. For the withstand
voltage of insulation wires, see the table below.
Applied Voltage (Vrms or VDC) Basic Insulation Double (reinforced) Insulation
0 to 150 1350 Vrms 2700 Vrms
151 to 300 1500 Vrms 3000 Vrms
301 to 600 2210 Vrms 3700 Vrms
To avoid electric shock when removing the terminal plate for wiring, be sure to
attach the terminal plate before inputting signals. Electric shock or fire can result
if signals are applied to the terminals when the terminal plate is removed from
the input modules.
To prevent fire, use signal wires of the temperature rating 80°C or better.
CAUTION
If a large pulling force is applied to the signal wires connected to the terminal
plate, the terminal plate or signal wire may break. To prevent this from
happening, fix all the wiring cables to the installation panel.
Do not apply a voltage exceeding the value indicated below to the input
terminals of the 10-CH Medium-Speed Universal Input module which attached
the plate with clamp terminals for current. Doing so can damage the modules.
Maximum input voltage
772081: ±1.5 VDC (continuation)
772082: ±5 VDC (continuation)
772083: ±8 VDC (continuation)
The MX100 and MW100 are a measurement category II (IEC61010-2-30) and
overvoltage category II (IEC61010-1) instrument.
Wiring Procedure
Wiring Procedure
For information about wiring, see the MX100 Data Acquisition Unit Installation and
Connection Guide (IM MX100-72E) provided with the main module, the MX100 Data
Acquisition Unit User’s Manual (IM MX100-01E) or the MX100 Data Acquisition Unit
User’s Manual (IM MW100-01E) contained in the manual CD-ROM.
Wiring of DC Current Input
• DC current input
DC current input
+
NC