Owner manual
11-7
IM MX190-01E
DARWIN Constants and Types
11
RTD Range
Mnemonic Description Setting range
DAQDARWIN_RANGE_RTD_1MAPT Pt100:1mA –200.0 to 600.0°C
DAQDARWIN_RANGE_RTD_2MAPT Pt100:2mA –200.0 to 250.0°C
DAQDARWIN_RANGE_RTD_1MAJPT JPt100:1mA –200.0 to 550.0°C
DAQDARWIN_RANGE_RTD_2MAJPT JPt100:2mA –200.0 to 250.0°C
DAQDARWIN_RANGE_RTD_2MAPT50 Pt50:2mA –200.0 to 550.0°C
DAQDARWIN_RANGE_RTD_1MAPTH Pt100:1mA-H –140.00 to 150.00°C
DAQDARWIN_RANGE_RTD_2MAPTH Pt100:2mA-H –70.00 to 70.00°C
DAQDARWIN_RANGE_RTD_1MAJPTH JPt100:1mA-H –140.00 to 150.00°C
DAQDARWIN_RANGE_RTD_2MAJPTH JPt100:2mA-H –70.00 to 70.00°C
DAQDARWIN_RANGE_RTD_1MANIS Ni100:1mA-S –200.0 to 250.0°C
DAQDARWIN_RANGE_RTD_1MANID Ni100:1mA-D –60.0 to 180.0°C
DAQDARWIN_RANGE_RTD_1MANI120 Ni120:1mA –70.0 to 200.0°C
DAQDARWIN_RANGE_RTD_CU10GE Cu10:GE –200.0 to 300.0°C
DAQDARWIN_RANGE_RTD_CU10LN Cu10:L&N –200.0 to 300.0°C
DAQDARWIN_RANGE_RTD_CU10WEED Cu10:WEED –200.0 to 300.0°C
DAQDARWIN_RANGE_RTD_CU10BAILEY Cu10:BAILEY –200.0 to 300.0°C
DAQDARWIN_RANGE_RTD_J263B J263*B –0.0 to 300.0 K
Contact Input (DI) Range
Mnemonic Description Setting range
DAQDARWIN_RANGE_DI_LEVEL Voltage input Less than 2.4 V, Greater
than or equal to 2.4 V
DAQDARWIN_RANGE_DI_CONTACT Contact input 0:open, 1:close
Strain input range
Mnemonic Description
Setting range
DAQDARWIN_RANGE_STRAIN_2K 2k
–2000 to 2000 µStrain (One-Gauge Method)
–1000 to 1000 µstrain (two-gauge method),
–500 to 500 µstrain (4-gauge method)
DAQDARWIN_RANGE_STRAIN_20K 20k
–20000 to 20000 µstrain (1-gauge method)
–10000 to 10000 µstrain (2-gauge method)
–5000 to 5000 µstrain (4-gauge method)
DAQDARWIN_RANGE_STRAIN_200K 200k
–200000 to 200000 µstrain (1-gauge method)
–100000 to 100000 µstrain (2-gauge method)
–50000 to 50000 µstrain (4-gauge method)
Pulse range
Mnemonic Description Setting range
DAQDARWIN_RANGE_PULSE_RATE RATE 0 - 30000
DAQDARWIN_RANGE_PULSE_GATE GATE 0 - 30000
11.2 DARWIN Constants