User Manual

<3. Parameters>
3-8
IM 11M12D01-51E
3.2.2 Multidrop Mode
Field devices in multidrop mode refer to the connection of several eld devices on a single
communication line. Up to 15 eld devices can be connected when set in multidrop mode. To activate
multidrop communication, each eld device address must be changed to a unique number in the
range 1 to 15. This change deactivates the 4 to 20mA output and changes it to 4mA.
Setting of Multidrop Mode
Call up Poll addr display.
1.Device setup ---> 4.Detailed setup ---> 4.Output condition ---> 1.HART output
--->1.Poll addr
Call up “Auto Poll” display.
HART output ---> Online Menu ---> Main Menu ---> 4.Utility ---> 1.Congure Communication
---> 1.Polling
"
1
"
(ENTER) (SEND)
Set the polling address (a
number from 1 to 15) and
press
ENTER (F4)
.
Then Press
SEND (F2).
F2
F030210-1.ai
AV550G:
Poll addr
0
0
ESC
DELHELP ENTER
Display
Operation
1
(HOME)
Return
" Online Menu "
with
HOME (F3)
.
2
Return to
" Main Menu "
with
a
" previous"
key.
3
Select
" Utility "
.
F3
F030211-1.ai
JLK
4
AV550G:
HART output
1 Poll addr 1
2 Num req preams 5
3 Burst mode On
4 Burst option PV
HOME
SENDHELP
AV550G:
1
Device setup
Online
2 PV
3 PV URV
4 PV LRV
21.64
21
0
%
%
%
SAVE
HART Communicator
1 Offline
2 Online
3 Frequency Device
4 Utility
Display
Operation