3.2 Setting Parameters
3.2.1 Burst Mode
The AV550G continuously sends the data stored in it when burst mode is setOn”. Either one of
measured value, % output value, or 4 to 20 mA output value can be selected and sent. The data
is sent periodically at 75 ms intervals as a digital signal when the AV550G is set in burst mode.
Therefore, communication by the HART simultaneous communicator is also possible.
Setting of Burst Mode
Call up Burst optiondisplay.
1.Device setup ---> 4.Detailed setup ---> 4.Output condition ---> 1.HART output --->
4.Burst option
Display Operation
(ENTER)
Set data to be sent.
Measured value (PV)
% output value
(% range/current)
4 to 20 mA output value
(Process vars /crnt)
Call up
" Burst mode"
display.
3.HART output 3.Burst mode
1
(ENTER)
Set
"
On
"
and press
ENTER
(F4).
2
(SEND)
Press
SEND (F2).
F4
F4
F2
F030209-1.ai
AV550G:
Burst option
PV
% range/current
Process vars/crnt
ENTER
ESCHELP
AV550G:
Burst mode
Off
ENTER
ESC
off
on
AV550G:
HART output
1 Poll addr 0
2 Num req preams 5
3 Burst mode On
4 Burst option PV
HOME
SENDHELP
********