5.4 Wiring for Contact Output
The equipment can output a maximum of two contact signals. These contact outputs can be used for
different applications such as a low alarm or high alarm.
Do the contact output wiring according to the following requirements.
DO-1
DO-1
DO-2
DO-2
F5.6E.ai
#2 Output
Analyzer
Terminal box
Annunciator or the like
#1 Output
Figure 5.6 Contact Output Wiring
5.4.1 Cable Specications
The number of cores varies depending on the number of contacts used.
5.4.2 Wiring Procedure
(1) M4 screws are used for the terminals. Use crimp-on terminals appropriate for M4 terminal
screws for cable connections.
(2) The contact output relays are rated 30 V DC 3A, 250 V AC 3A. Connect a load (e.g. pilot lamp
and annunciator) within these limits.
5.5 Wiring for Contact Input
The converter can execute specied function when receiving contact signals.
To use these contact signals, proceed wiring as follows:
Converter Terminal box
DI-1
DI-C
DI-2
Contact input 1
Contact input 2
F5.7E.ai
Figure 5.14 Contact Input Wiring
5.5.1 Cable Specications
Use a 2-core or 3-core cable for this wiring. Depending on the number of input(s), determine which
cable to use.