Owner manual
Table Of Contents
- Introduction
- CONTENTS
- 1. Overview
- 2. Specifications
- 2.1 General Specifications
- 2.2 General use Separate type Detector and Related Equipment
- 2.3 Separate type Detector for High Temperature and Related Equipment
- 2.4 ZR402G Separate type Converter
- 2.5 ZA8F Flow Setting Unit and ZR40H Automatic Calibration Unit
- 2.6 ZO21S Standard Gas Unit
- 2.7 Other Equipments
- 2.7.1 Dust Filter for the Detector (K9471UA)
- 2.7.2 Dust Guard Protector (K9471UC)
- 2.7.3 Ejector Assembly for High Temperature (E7046EC, E7046EN)
- 2.7.4 Stop Valve (L9852CB, G7016XH)
- 2.7.5 Check Valve (K9292DN, K9292DS)
- 2.7.6 Air Set
- 2.7.7 Zero Gas Cylinder (G7001ZC)
- 2.7.8 Cylinder Pressure Reducing Valve (G7013XF, G7014XF)
- 2.7.9 Case Assembly for Calibration Gas Cylinder (E7044KF)
- 2.7.10 ZR22A Heater Assembly
- 3. Installation
- 3.1 Installation of General-purpose Detector
- 3.2 Installation of High Temperature Detector (ZR22G-015)
- 3.3 Installation of the ZR402G Converter
- 3.4 Installation of ZA8F Flow Setting Unit
- 3.5 Installation of ZR40H Automatic Calibration Unit
- 3.6 Installation of the Case Assembly(E7044KF)
- 3.7 Insulation Resistance Test
- 4. Piping
- 5. Wiring
- 6. Components
- 7. Startup
- 7.1 Checking Piping and Wiring Connections
- 7.2 Checking Valve Setup
- 7.3 Supplying Power to the Converter
- 7.4 Touchpanel Switch Operations
- 7.5 Confirmation of Converter Type Setting
- 7.6 Confirmation of Detector Type Setting
- 7.7 Selection of Sample Gas
- 7.8 Output Range Setting
- 7.9 Setting Display Item
- 7.10 Checking Current Loop
- 7.11 Checking Contact I/O
- 7.12 Calibration
- 8. Detailed Data Setting
- 9. Calibration
- 10. Other Functions
- 11. Inspection and Maintenance
- 12. Troubleshooting
- Customer Maintenance Parts List CMPL 11M12A01-02E
- Customer Maintenance Parts List CMPL 11M12C01-01E
- Customer Maintenance Parts List CMPL 11M12A01-11E
- Customer Maintenance Parts List CMPL 11M03B01-10E
- Customer Maintenance Parts List CMPL 11M03B01-05E
- Customer Maintenance Parts List CMPL 11M03D01-01E
- Revision Information

<12. Troubleshooting>
12-3
IM 11M12A01-02E 8th Edition : Jan.13,2012-00
12.1.2.2 Error2: Heater Temperature Failure
This error occurs if the detector heater temperature does not rise during warm-up, falls below 730
°C after warm-up, or exceeds 780 °C. When Error2 occurs, Alarm 10 (cold junction temperature
alarm) or Alarm 11 (thermocouple voltage alarm) may be generated at the same time. Be sure to
press the error indication to get the error description and conrm whether or not these alarms are
being generated simultaneously.
If Alarm 10 is generated simultaneously, a failure in the cold junction system on the detector
terminal block is suspected. In this case, follow the procedure according to troubleshooting for
Alarm 10 in Section 12.2.2.5.
If Alarm 11 is generated simultaneously, a failure in the thermocouple system located in the
detector heater is suspected. In this case, follow the procedure according to troubleshooting for
Alarm 11 in Section 12.2.2.6
If this failure occurs immediately after the power is supplied, the polarity at thermocouple input
connection (TC+, TC-) on the converter may be reversed. Check the connection from the
detector.
Causes considered for cases where Error2 occurs independently are shown below.
(1) Faulty heater in the detector (heater wire breakage)
(2) Faulty thermocouple in the detector
(3) Faulty cold junction sensor located at the detector terminal block.
(4) Failure in electrical circuits inside the converter
(5) Heater temperature control overcurrent limiting triggered.
(6) TC+ ,TC- thermocouple terminals wired to detector with reverse (wrong) polarity.
Overcurrent protection is triggered if there are problems in the heater wiring. When the protective
circuit is triggered, the internal fuse blows and the heater is disconnected, resulting in Error 2
(temperature failure).
<Locating cause of failure, and countermeasures>
(1) Turn off power to the converter.
(2) Remove the cable from terminals 7 and 8 of the detector and measure the resistance value
between these terminals. The heater unit is normal if the resistance is lower than about
90 Ω. If the resistance value is higher, failure of the heater unit is suspected. In this case,
replace the heater unit (refer to Section 11.1.3, Replacement of the Heater Unit). In addition,
check that the wiring resistance between the converter and detector is 10 Ω or less.
(3) Ensure that TC+ terminal (terminal 3 in detector) is connected to converter TC+ terminal,
and TC- terminal (terminal 4) is connected to converter TC- terminal.
(4) Remove the wiring from terminals 3 and 4 of the detector and measure the resistance
value between these terminals. The thermocouple is considered normal if the resistance
value is 5 Ω or less. If the value is higher than 5 Ω, it may indicate that the thermocouple
wire has broken or is about to break. In this case, replace the heater unit (refer to Section
11.1.3, Replacement of the Heater Unit). Also, check that the wiring resistance between the
converter and detector is 10 Ω or less.
(5) Even if items (2) to (4) are normal, the heater overcurrent protection fuse may have blown.
Check for wiring problems such as the following:
1) Heater terminals shorted.
2) Heater terminal(s) shorted to ground.
3) Heater terminals shorted to power supply.
If the internal fuse blows, this cannot be replaced by the user. Contact your Yokogawa service
representative.