Owner manual
Table Of Contents
- Introduction
- CONTENTS
- 1. Overview
- 2. Specifications
- 2.1 General Specifications
- 2.2 General use Separate type Detector and Related Equipment
- 2.3 Separate type Detector for High Temperature and Related Equipment
- 2.4 ZR402G Separate type Converter
- 2.5 ZA8F Flow Setting Unit and ZR40H Automatic Calibration Unit
- 2.6 ZO21S Standard Gas Unit
- 2.7 Other Equipments
- 2.7.1 Dust Filter for the Detector (K9471UA)
- 2.7.2 Dust Guard Protector (K9471UC)
- 2.7.3 Ejector Assembly for High Temperature (E7046EC, E7046EN)
- 2.7.4 Stop Valve (L9852CB, G7016XH)
- 2.7.5 Check Valve (K9292DN, K9292DS)
- 2.7.6 Air Set
- 2.7.7 Zero Gas Cylinder (G7001ZC)
- 2.7.8 Cylinder Pressure Reducing Valve (G7013XF, G7014XF)
- 2.7.9 Case Assembly for Calibration Gas Cylinder (E7044KF)
- 2.7.10 ZR22A Heater Assembly
- 3. Installation
- 3.1 Installation of General-purpose Detector
- 3.2 Installation of High Temperature Detector (ZR22G-015)
- 3.3 Installation of the ZR402G Converter
- 3.4 Installation of ZA8F Flow Setting Unit
- 3.5 Installation of ZR40H Automatic Calibration Unit
- 3.6 Installation of the Case Assembly(E7044KF)
- 3.7 Insulation Resistance Test
- 4. Piping
- 5. Wiring
- 6. Components
- 7. Startup
- 7.1 Checking Piping and Wiring Connections
- 7.2 Checking Valve Setup
- 7.3 Supplying Power to the Converter
- 7.4 Touchpanel Switch Operations
- 7.5 Confirmation of Converter Type Setting
- 7.6 Confirmation of Detector Type Setting
- 7.7 Selection of Sample Gas
- 7.8 Output Range Setting
- 7.9 Setting Display Item
- 7.10 Checking Current Loop
- 7.11 Checking Contact I/O
- 7.12 Calibration
- 8. Detailed Data Setting
- 9. Calibration
- 10. Other Functions
- 11. Inspection and Maintenance
- 12. Troubleshooting
- Customer Maintenance Parts List CMPL 11M12A01-02E
- Customer Maintenance Parts List CMPL 11M12C01-01E
- Customer Maintenance Parts List CMPL 11M12A01-11E
- Customer Maintenance Parts List CMPL 11M03B01-10E
- Customer Maintenance Parts List CMPL 11M03B01-05E
- Customer Maintenance Parts List CMPL 11M03D01-01E
- Revision Information

<8. Detailed Data Setting>
8-21
IM 11M12A01-02E
8.6.4 Setting Purging
Purging is to remove condensed water in the calibration gas pipe by supplying a span calibration
gas for a given length of time before warm-up of the detector. This prevents cell breakage during
calibration due to condensed water in the pipe.
Open the solenoid valve for the automatic calibration span gas during purging and after the purge
time has elapsed, close the valve to start warm-up.
Purging is enabled when the cell temperature is 100 °C or below upon power up and the purge
time is set in the range of 1 to 60 minutes.
Tag:
30
°C
4mA -Output1
4mA -Output2
Hold
Purge
F8.19.ai
Figure 8.19 Display during Purging
8.6.4.1 Procedure
Set the purging time as follows:
(1) Press the [Setup] key in the Basic panel display to display the Execution/Setup display.
(2) Select “Commissioning” in the Execution/Setup display. The Commissioning (Setup) display
then appears.
(3) Select “Others” in that display and the Others display then appears, as shown in Figure
8.20.
(4) Select “Purging”. The purging time setting display appears, as shown in Figure 8.21.
(5) Point to the “Purging time” and press the [Enter] key. Then the display for selecting purging
time appears.
(6) Enter the desired numeric value from the numeric-data entry display.
The allowable input ranges from 0 to 60 minutes.
Enter
Others
F8.20.ai
Clock
Averaging
Fuel setup
Purging
Unit setup
Passwords
Defaults
Enter
Purging time: 0 min
Purging
F8.21E.ai
Figure 8.20 Other Settings Figure 8.21 Purging Display
8th Edition : Jan.13,2012-00