Owner manual
Table Of Contents
- Introduction
- CONTENTS
- 1. Overview
- 2. Specifications
- 2.1 General Specifications
- 2.2 General use Separate type Detector and Related Equipment
- 2.3 Separate type Detector for High Temperature and Related Equipment
- 2.4 ZR402G Separate type Converter
- 2.5 ZA8F Flow Setting Unit and ZR40H Automatic Calibration Unit
- 2.6 ZO21S Standard Gas Unit
- 2.7 Other Equipments
- 2.7.1 Dust Filter for the Detector (K9471UA)
- 2.7.2 Dust Guard Protector (K9471UC)
- 2.7.3 Ejector Assembly for High Temperature (E7046EC, E7046EN)
- 2.7.4 Stop Valve (L9852CB, G7016XH)
- 2.7.5 Check Valve (K9292DN, K9292DS)
- 2.7.6 Air Set
- 2.7.7 Zero Gas Cylinder (G7001ZC)
- 2.7.8 Cylinder Pressure Reducing Valve (G7013XF, G7014XF)
- 2.7.9 Case Assembly for Calibration Gas Cylinder (E7044KF)
- 2.7.10 ZR22A Heater Assembly
- 3. Installation
- 3.1 Installation of General-purpose Detector
- 3.2 Installation of High Temperature Detector (ZR22G-015)
- 3.3 Installation of the ZR402G Converter
- 3.4 Installation of ZA8F Flow Setting Unit
- 3.5 Installation of ZR40H Automatic Calibration Unit
- 3.6 Installation of the Case Assembly(E7044KF)
- 3.7 Insulation Resistance Test
- 4. Piping
- 5. Wiring
- 6. Components
- 7. Startup
- 7.1 Checking Piping and Wiring Connections
- 7.2 Checking Valve Setup
- 7.3 Supplying Power to the Converter
- 7.4 Touchpanel Switch Operations
- 7.5 Confirmation of Converter Type Setting
- 7.6 Confirmation of Detector Type Setting
- 7.7 Selection of Sample Gas
- 7.8 Output Range Setting
- 7.9 Setting Display Item
- 7.10 Checking Current Loop
- 7.11 Checking Contact I/O
- 7.12 Calibration
- 8. Detailed Data Setting
- 9. Calibration
- 10. Other Functions
- 11. Inspection and Maintenance
- 12. Troubleshooting
- Customer Maintenance Parts List CMPL 11M12A01-02E
- Customer Maintenance Parts List CMPL 11M12C01-01E
- Customer Maintenance Parts List CMPL 11M12A01-11E
- Customer Maintenance Parts List CMPL 11M03B01-10E
- Customer Maintenance Parts List CMPL 11M03B01-05E
- Customer Maintenance Parts List CMPL 11M03D01-01E
- Revision Information

<8. Detailed Data Setting>
8-20
IM 11M12A01-02E
8.6.3.2 Procedure
To make a fuel setting, follow these steps:
(1) Press the [Setup] key in the Basic panel display to display the Execution/Setup display.
(2) Select “Commissioning” in the Execution/Setup display. The Commissioning (Setup) display
then appears.
(3) Select “Others” in that display and then the Fuel setup shown in Figure 8.17.
(4) Choose the “Theoretical air quantity required” and the “Contents of moisture in exhaust gas”
in turn. The numeric-data entry display then appears. Enter numeric data using the numeric
keys.
(5) Choose “more” in the Fuel setup display. The Fuel setup shown in Figure 8.18 then appears.
(6) Set the numeric data to the “Value of the X coefcient” and then to the “Absolute humidity of
the atmosphere”.
(7) Choose “nished” to return to the display shown in Figure 8.17.
See Manual for details!
Contents of moisture in
exhaust gas: 1. 0 0 m
3
/kg
Theoretical air quantity
required: 1. 0 0 m
3
/kg
more.....
Enter
Fuel setup
F8.17E.ai
Value of the X coefficient:
1 . 0 0
Absolute humidity of the
atmosphere:
0. 1 0 0 0 kg/kg
finished.
Enter
Fuel setup
F8.18E.ai
Figure 8.17 Fuel Setup Figure 8.18 Fuel Setup
8.6.3.3 Default Values
When the analyzer is delivered, or if data are initialized, default, parameter settings are as shown
in Table 8.9.
Table 8.9 Default Settings for Fuel Values
Item Default setting
Amount of water vapor in exhaust gas 0.00 m
3
/kg (m
3
)
Theoretical amount of air 1.00 m
3
/kg (m
3
)
X value 1.00
Absolute humidity of the atmosphere 0.0 kg/kg
8th Edition : Jan.13,2012-00