Owner manual
Table Of Contents
- Introduction
- CONTENTS
- 1. Overview
- 2. Specifications
- 2.1 General Specifications
- 2.2 General use Separate type Detector and Related Equipment
- 2.3 Separate type Detector for High Temperature and Related Equipment
- 2.4 ZR402G Separate type Converter
- 2.5 ZA8F Flow Setting Unit and ZR40H Automatic Calibration Unit
- 2.6 ZO21S Standard Gas Unit
- 2.7 Other Equipments
- 2.7.1 Dust Filter for the Detector (K9471UA)
- 2.7.2 Dust Guard Protector (K9471UC)
- 2.7.3 Ejector Assembly for High Temperature (E7046EC, E7046EN)
- 2.7.4 Stop Valve (L9852CB, G7016XH)
- 2.7.5 Check Valve (K9292DN, K9292DS)
- 2.7.6 Air Set
- 2.7.7 Zero Gas Cylinder (G7001ZC)
- 2.7.8 Cylinder Pressure Reducing Valve (G7013XF, G7014XF)
- 2.7.9 Case Assembly for Calibration Gas Cylinder (E7044KF)
- 2.7.10 ZR22A Heater Assembly
- 3. Installation
- 3.1 Installation of General-purpose Detector
- 3.2 Installation of High Temperature Detector (ZR22G-015)
- 3.3 Installation of the ZR402G Converter
- 3.4 Installation of ZA8F Flow Setting Unit
- 3.5 Installation of ZR40H Automatic Calibration Unit
- 3.6 Installation of the Case Assembly(E7044KF)
- 3.7 Insulation Resistance Test
- 4. Piping
- 5. Wiring
- 6. Components
- 7. Startup
- 7.1 Checking Piping and Wiring Connections
- 7.2 Checking Valve Setup
- 7.3 Supplying Power to the Converter
- 7.4 Touchpanel Switch Operations
- 7.5 Confirmation of Converter Type Setting
- 7.6 Confirmation of Detector Type Setting
- 7.7 Selection of Sample Gas
- 7.8 Output Range Setting
- 7.9 Setting Display Item
- 7.10 Checking Current Loop
- 7.11 Checking Contact I/O
- 7.12 Calibration
- 8. Detailed Data Setting
- 9. Calibration
- 10. Other Functions
- 11. Inspection and Maintenance
- 12. Troubleshooting
- Customer Maintenance Parts List CMPL 11M12A01-02E
- Customer Maintenance Parts List CMPL 11M12C01-01E
- Customer Maintenance Parts List CMPL 11M12A01-11E
- Customer Maintenance Parts List CMPL 11M03B01-10E
- Customer Maintenance Parts List CMPL 11M03B01-05E
- Customer Maintenance Parts List CMPL 11M03D01-01E
- Revision Information

<8. Detailed Data Setting>
8-9
IM 11M12A01-02E
8.4 Output Contact Setup
8.4.1 Output Contact
Mechanical relays provide contact outputs. Be sure to observe relay contact ratings. (For details,
see Section 2.1, General Specications) The operation modes of each contact output are as
follows. For output contacts 1 to 3 you can select open or closed contact when the contact is
“operated”. Default is closed. For output contact 4, contact is closed.
When power fails, contact outputs 1 to 3 are open, and 4 is closed.
Table 8.4
State when contact “ operated ”
When no power is applied
to this equipment
Output contact 1 Open (deenergized) or closed (energized) selectable. Open
Output contact 2 Open (deenergized) or closed (energized) selectable. Open
Output contact 3 Open (deenergized) or closed (energized) selectable. Open
Output contact 4 Closed (deenergized) only Closed
8.4.2 Setting Procedure
To set the output contact, follow these steps.
(1) Press the [Setup] key in the Basic panel display to display the Execution/Setup display.
(2) Select “Commissioning” in the Execution/Setup display. The Commissioning (Setup) display
then appears.
(3) Select the “Contact setup” in the Commissioning (Setup) display. The Contact setup display
shown in Figure 8.6 then appears.
(4) Select the desired output contact. This section shows an example where “Output contact1”
is selected (see Figure 8.7).
(5) Each set item and the selected items are briey described in Table 8.5. The following
describes an example of setting where Output contact 1 is closed during calibration.
(6) Select “Others” in the Output contact 1 display. The “Contact1 Others” display shown in
Figure 8.8 then appears. Select “Calibration” in the Contact1 Others display.
(7) The ON or OFF selection display then appears. Select “ON” herein.
(8) Press the [Reject] key to go back to the previous display.
(9) Move the pointer to “During power-off the contact is open and in condition it is Open” and
press the [Enter] key. The “OFF” or “ON” selection display then appears. If you select “OFF,”
this means “Open” in normal conditions and “Closed” when the contact output is on.
CAUTION
• The contact output 4 is xed as “ close in power ON”, which cannot be changed by setting.
8th Edition : Jan.13,2012-00