Owner manual

Table Of Contents
<8. Detailed Data Setting>
8-9
IM 11M12A01-02E
8.4 Output Contact Setup
8.4.1 Output Contact
Mechanical relays provide contact outputs. Be sure to observe relay contact ratings. (For details,
see Section 2.1, General Specications) The operation modes of each contact output are as
follows. For output contacts 1 to 3 you can select open or closed contact when the contact is
“operated”. Default is closed. For output contact 4, contact is closed.
When power fails, contact outputs 1 to 3 are open, and 4 is closed.
Table 8.4
State when contact operated
When no power is applied
to this equipment
Output contact 1 Open (deenergized) or closed (energized) selectable. Open
Output contact 2 Open (deenergized) or closed (energized) selectable. Open
Output contact 3 Open (deenergized) or closed (energized) selectable. Open
Output contact 4 Closed (deenergized) only Closed
8.4.2 Setting Procedure
To set the output contact, follow these steps.
(1) Press the [Setup] key in the Basic panel display to display the Execution/Setup display.
(2) Select “Commissioning” in the Execution/Setup display. The Commissioning (Setup) display
then appears.
(3) Select the “Contact setupin the Commissioning (Setup) display. The Contact setup display
shown in Figure 8.6 then appears.
(4) Select the desired output contact. This section shows an example where “Output contact1
is selected (see Figure 8.7).
(5) Each set item and the selected items are briey described in Table 8.5. The following
describes an example of setting where Output contact 1 is closed during calibration.
(6) Select “Others” in the Output contact 1 display. The “Contact1 Others” display shown in
Figure 8.8 then appears. Select “Calibration” in the Contact1 Others display.
(7) The ON or OFF selection display then appears. Select “ONherein.
(8) Press the [Reject] key to go back to the previous display.
(9) Move the pointer to “During power-off the contact is open and in condition it is Open” and
press the [Enter] key. The “OFFor “ON” selection display then appears. If you select “OFF,”
this means “Openin normal conditions and “Closedwhen the contact output is on.
CAUTION
The contact output 4 is xed as close in power ON”, which cannot be changed by setting.
8th Edition : Jan.13,2012-00