<3 INSTALLATION AND WIRING> 3-22
3.12  Cyclops Division 2/Zone 2 Purge Indictor, with switch
Type Z purging reduces the classifi cation within a protected electronics enclosures from Division 2 or Zone 2 
to nonhazardous. Failure to maintain pressure within the protected enclosure shall be detected by an alarm 
or indicator at the electronics enclosure. The dilution purge time shall be a manual operation and once the 
electronics enclosure has been purged of ignitable or fl ammable concentrations, only positive pressure of at least 
0.20 inches H
2
O (0.50 mbar) is required to be maintained within the electronics enclosure and it is not necessary 
to remove power from the protected equipment upon the loss of purge pressure. The CYCLOPS 
Z – Purge Indicator is used to provide safe monitoring of electrical equipment in Division 2 and Zone 2 hazardous 
areas, which can be used to prevent the possibility of fi re or explosion inside the enclosure of energized electrical 
equipment, a protective gas supply is used to dilute potentially fl ammable materials to an acceptable level, 
creating a safe area for the electrical equipment within the enclosure. Positive pressure prevents the ingress 
of fl ammable materials in the surrounding atmosphere from entering into the enclosure, as long as positive 
pressure is maintained. After the enclosure is purged, power may be manually applied to the protected electrical 
equipment.
The CYCLOPS Z – Purge Indicator provides an objective evidence of the presence of adequate positive purge 
pressure within the electrical equipment enclosure. A normally open differential pressure switch continuously 
compares the pressure inside the monitored electronics enclosure with respect to the atmospheric pressure 
surrounding the electronics enclosure. When the monitored electronics enclosure register’s a pressure of at 
least 0.20 inches H
2
O (0.50 mbar) above the reference atmospheric pressure a manually controlled dilution 
time cycle may then begin. Typically, a minimum dilution time cycle is specifi ed to ensure that at least fi ve 
times the volume of free space in the electronics enclosure is exchanged before power is manually applied to 
the electrical equipment. (The number of exchanged volumes may be higher in some situations). After the 
manual dilution time cycle has elapsed and the monitored electronics enclosure pressure is being maintained 
above 0.20 inches H
2
O (0.50 mbar), power may be manually applied to the electrical equipment within the 
purged electronics enclosure. The CYCLOPS Z – Purge Indicator is designed to indicate the presence of purge 
pressure from one pressure reference point. Several electronics enclosures can be installed in series with purge 
gas being introduced into the fi rst electronics enclosure and the CYCLOPS Z – Purge Indicator monitoring the 
last electronics enclosure in the series; multiple electronics enclosures can now be monitored using only one 
CYCLOPS Z – Purge Indicator. The pressure inside the monitored electronics enclosures must maintain at least 
0.20 inches H
2
O (0.50 mbar) higher than the atmospheric pressure surrounding the electronics enclosure. This 
ensures that hazardous materials are not going to ingress into the pressurized and now protected electronics 
enclosures. If any of the electronics enclosures installed in the series door is opened, pressure will show to be 
below the required 0.20 inches H
2
O (0.50 mbar) in all electronics enclosures. The exhaust vent which comes as 
part of the CYCLOPS Z – Purge Indicator casing, can exhaust purge gas from enclosures with volumes up to 15 
cubic feet (425 liters).
Cyclops Features
Certifi ed for installation and use in ATEX and IECEx for
Type Z – Purge, II 3 G Ex nA nL [pz] IIC T6 
For Zone 2 gas hazardous areas
Certifi ed for installation and use in ATEX and IECEx for
Type Z – Purge, II 3 G Ex nA nL [pz] IIC T6 
For Zone 2 gas hazardous areas
IM 11Y01B02-11E-A 5th Edition :June 5, 2012-00