Instruction Manual
  <1. Overview>
1-50
IM 11B08A01-01E
  In the case where a stream specifi cation change command (for N times of measurement) 
is received during the run mode in the stream specifi cation status (for N times of 
measurement) [3C2]
  The measurement status is changed to the requested stream specifi cation status (for N 
times of measurement) when the Nth round of the measurement of the currently-measured 
stream is completed.
  In this case, the operation mode changes from the run mode to the stop mode when the Nth 
round of the specifi ed measurement is completed.
Stop StopRun
W4W1
S1
W1
S1
W1
S1 S4
W4
S4
[3C2]
Time
Stream specification 1 (3 times) Stream specification 4 (Twice)
Assinning stream specification 4 (Twice)
Run command
  In the case where a stream specifi cation change command is received during the stop 
mode in the stream specifi cation status [2B1]
  The measurement status is immediately changed to the requested stream specifi cation 
status.
  In this case, the operation mode remains unchanged from the stop mode.
[2B1]
Time
Stream specification 1 Stream specification 4
Assinning stream specification 4
Stop
  In the case where a stream specifi cation change command is received during the pause 
mode in the stream specifi cation status [2B6]
  The measurement status is immediately changed to the requested stream specifi cation 
status.
  In this case, the operation mode changes to the stop mode and valves are all closed (turned 
off).
Run
[2B6]
Time
Stream specification 1 Stream specification 4
Assinning stream specification 4
Stop
  In the case where a stop command is received during the run mode in the stream 
specifi cation status (for continuous measurement) [2E2]
  The operation mode is immediately prepared to be changed to the stop mode.
  The operation mode changes to the stop mode in the stream specifi cation status (for 
continuous measurement) when the measurement of the currently-measured stream is 
completed.
  The stop command can be canceled with a cancel command until the operation mode 
changes to the stop mode.
2nd Edition : May 11, 2012-00