Instruction Manual

<1. Overview>
1-45
IM 11B08A01-01E
In the case where a forced stop command is received during the pause mode in the stream
sequence status [1F6]
The operation mode is immediately changed to the stop mode in the stream sequence
status.
Pause
[1F6]
Time
Stream sequence 1
Forced stop command
Stop
In the case where a pause command is received during the stop mode in the stream
sequence status [1H1]
The operation mode is immediately changed to the pause mode in the stream sequence
status.
PauseStop Run
W2 W3
S2S1
W1 W2
S1S1
[1H1]
Time
Stream sequence 1
Pause command
Run command
Pause time
In the case where a pause command is received during the run mode in the stream
sequence status [1H2]
The operation mode is immediately prepared to be changed to the pause mode in the
stream sequence status.
The operation mode changes to the pause mode in the stream sequence status at a preset
time during the measurement of the currently-measured stream.
The pause command can be canceled with a cancel command until the operation mode
changes to the pause mode.
In the case where a run command is received during the pause mode in the stream
sequence status [1G6]
The suspended measurement is resumed.
Run RunPause
Rest of W2
Rest of S1
W1 W2 W3
S2 S3S1
W3
S2
W1 W2
S1
[1G6]
Time
Stream sequence 1
Run command
[1H2]
Pause command
2nd Edition : May 11, 2012-00