5.4.15 D/O Setup 
11/11/22
15:15:45
D/O Setup 
Slot # 1     DO # 1
> - Process assign  Operation mode
 - GCM number  1
 - Operation mode  Stop
Menu Status Slot# DO#
F1 F2 F3 F4 F5 F6
Figure 5.89 
Example of D/O setup screen
F1 (Menu):  Displays the Table menu screen.
F3 (Status):  Displays the D/O status screen.
F5 (Slot #):  Specifi es a slot number.
F6 (DO #):  Specifi es a D/O number.
•  A D/O contact number displays the relative number of each SLOT.
•  When F5 (Slot #) is pressed, Slot #: is displayed at the bottom line. When a slot number 
is entered and SET/ENT key is pressed, the set value of the specifi ed slot number is 
displayed.
•  When setting the slot number, if a card other than D/O or DI/O is installed in the relevant 
slot, any entry is not accepted.
•  When F6 (DO#) is pressed, DO #: is displayed at the bottom line (the default is 1). When 
D/O number is entered and SET/ENT key is pressed, the set value of the specifi ed D/O 
number is displayed.
•  When any D/O number is used for stream identifi cation on the GCM setup screen , the 
Process assign displays ****** and not selectable.
11/11/22
15:15:45
D/O Setup  (1/2)
11/11/22
15:15:45
D/O Setup  (2/2)
Slot # 1  DO # 1 Slot # 1  DO # 1
> - Process assign  Stream sequence > - Stream sequence 7  AAAAAAA
 - GCM number  1  - Stream sequence 8  AAAAAAA
 - Stream sequence 1  AAAAAAA
 - Stream sequence 2  AAAAAAA
 - Stream sequence 3  AAAAAAA
 - Stream sequence 4  AAAAAAA
 - Stream sequence 5  AAAAAAA
 - Stream sequence 6  AAAAAAA
Menu Status Slot# DO# Menu Status Slot# DO#
F1 F2 F3 F4 F5 F6 F1 F2 F3 F4 F5 F6
Figure 5.90 
Example of D/O setup screen (setting the Process assign to stream sequence)
When the stream sequence is set in the Process assign, items to set up specifi ed output of each 
stream sequence are added, and all two pages are displayed.