Instruction Manual
  <5. EtherLCD>
5-24
IM 11B08A01-01E
 TIP
For this operation, the user level C or higher is required.
•  On the initial screen, the smallest slot number among those of the A/O cards inserted is 
displayed.
•  For the slot number setting, only slot numbers of A/O cards can be accepted.
Display Item Name Set Lower Limit Upper Limit Unit Remarks
Slot Slot number 1 5 Absolute slot number
AO # A/O channel number 1 8 Number Relative channel number
Set value  –0.2500 1.2500 After the value is set, 0 to 1 is 
output as 4 to 20 mA.
5.3.3 D/O Operation
Navigating to the D/O Operation screen sets the mode to D/O Manual and all the D/O contacts 
(up to 25) are turned off. On the D/O Operation screen, both the On and Off commands are 
available. Navigating to other screens cancels the D/O Manual mode, and according to the 
settings, each D/O contact is turned On or Off.
To change the D/O status to On or Off, select the D/O number with the cursor and press the Set/
Ent key. Note that this operation must be done in Manual status and in Stop mode.
11/11/22
15:15:45
D/O Operation 
Slot N 
 DO#  Status
> - 1  A
 - 2  A
 - 3  A
 - 4  A
 - 5  A
Menu Slot#
F1 F2 F3 F4 F5 F6
Figure 5.28 
Example of the D/O Operation screen
F1 (Menu):  Displays the Operation Menu screen.
F6 (Slot #):  Sets a slot number.
 TIP
For this operation, the user level C or higher is required.
•  On the initial screen, the smallest slot number among those of the D/O cards inserted is 
displayed.
•  For the slot number setting, only slot numbers of D/O cards can be accepted.
Display Item Name Set Lower Limit Upper Limit Unit Remarks
Slot Slot number 1 5 Absolute slot number
DO # D/O contact number 1 5 Number Relative D/O contact number
Status  0: Off
1: On