Instruction Manual

<5. EtherLCD>
5-7
IM 11B08A01-01E
5.2.3 D/I Status
The D/I (contact input) status is displayed on the screen.
11/11/22
15:15:45
D/I Status
Slot # 1
DI# Name Value Processing name
1 a1 Open Stream sequence
2 Open No assignment
3 Open No assignment
4 Open No assignment
5 Open No assignment
6 Open No assignment
7 Open No assignment
8 Open No assignment
Menu Table Slot#
F1 F2 F3 F4 F5 F6
Figure 5.7
Example of the D/I status screen
F1 (Menu): Displays the Status Menu screen.
F4 (Table): Displays the D/I Setup screen.
F6 (Slot #): Sets a slot number.
TIP
The Value data are refreshed automatically at a xed interval (1 second).
On the initial screen, the smallest slot number among those of the D/I cards inserted is displayed.
For the slot number setting, only slot numbers of D/I or DI/O cards can be accepted.
Up to CH3 are displayed for DI/O cards.
If no D/I cards are inserted, the Status Menu screen displays “Not load” on the bottom.
Display Item Name Set Lower Limit Upper Limit Unit Remarks
Slot # Slot number 1 5 Absolute slot number
DI # D/I contact number 1 8 Relative channel number
Name D/I name 8 single-byte alphanumeric
characters
Status Status Open/Close
Processing
name
Processing name No assignment, Stream
sequence, Stream, Range
change Cal/Val, Operation
mode change, Alarm process
2nd Edition : May 11, 2012-00
5