<4. Engineering>
4-6
IM 11B06E01-01E
4.2.3 Setting
Thisleconsistsoftextcharacters.Editingcanbedonewith“Notepad”software,but“MS-Excel”
softwareisrecommended.Theeditedleshouldbesavedwith“CSV”asanextension.
Eachlinehasmeaninginthemaple.Alinebeginningwithcharacter#isinterpretedasamean-
ingful line.
Andacommentlinedoesnotbeginwithcharacter“#“.
NOTE
Commentlinesmustnotincludethe#character,otherwiseASGWmaynotworkproperly.
#SLAVE, n
This n is the Slave ID when DCS accesses to ASGW with Modbus interface and commonly
uses on the 2 communication ports. Range is 1 to 247.
#RETRY, m
This m is the number of retry times when a write error occurs. Range is 1 to 32767.
#TOUT, t
This t is character time-out in the communication between DCS and Modbus RTU. Adjust the
value depending on communication speed. Unit is ms [millisecond] and range is 10 to 5000.
#KEEP_BIT, t
Thisspeciestheholdingtimeofthevariabledatabits.Thististhetime(sec)tohold.
This function can be used on Rev. 1.01.04 or later of ASGW. The default value is 5 sec, and
range is 0 to 3276.
#TCP_TIMEOUT, t
Thisspeciestime-outvalueofModbusTCP.Thististhetime-outvalue(sec).
This function can be used on Rev. 1.01.03 or later of ASGW. The default value is 30 sec, and
range is 1 to 100.
#TSET, StnID
Writing in address 00001 of the coil in the Modbus address table carries out time setting in all
devicesthathaveatimesettingfunction.IfStnIDissetto255inthe#TSETline,timesetting
iscarriedoutforalldevices;ifStnIDissettoanynumberfrom1to254,thesettingiseffec-
tiveonlyforaspecieddevice.
l Specifying analyzers and PCASs
Upto31analyzersandPCASscanbespeciedtobeconnected.
AuniqueStnIDnumbermustbeallocatedtoeachanalyzerandPCAS.ThisStnIDiskeydataon
Modbus interface.
Format=“#STN,StnID,StnType,IP_Address”
#STN Keyword.Thelinestartfrom“#STN”isrecognizedasoneforspecifyinganalyzers.
StnID ID number of analyzer (1-254)
StnType Type:GC8000/GC1000/ASIU/GCIU/PCAS
IP_Address IPaddressofanalyzer
Example“#STN,3,GC1000,192.168.0.1”