Manual

<9. In-Process Operation>
9-3
IM 01S01C01-01EN
Table 9.2 Field Diagnostic Alert
Indication of FD_*_ACTIVE Indication of FD_RECOMMEN_ACT Solution
Electronics failure Repair electronics Replace electrical parts e.g. amplier.
Or contact sales ofce or service
center.
Sensor/Actuator failure Repair Sensor/Actuator Replace mechanics e.g. sensor or
actuator. Or contact sales ofce or
service center.
Potential failure Investigate failure Perform reconguration, cleaning,
wiring/connector or electrical board
check.
If alarm still persists, contact sales
ofce or service center.
Backup function in operation Repair primary side Repair primary sensor before backup
sensor fails.
Firmware update error Retry updatingrmware Retry rmware update. Check cause of
the failure if alarm persists.
Communication conguration error Congure communication correctly Correct conguration of
communication.
Non-operating-state Wait for a while Wait for a while. Check cause of the
failure if alarm persists.
Calibration warning Check calibration Investigate cause of failure and
recalibrate device.
Device conguration error Congure device correctly Correct conguration relating to sensor
or actuator.
Function restricted Conrm the state Check if this is right state.
Simulation mode Conrm the state Check if this is right state.
Manual mode Conrm the state Check if this is right state.
Function Block notice Check Function Block status Check conditions of function
blocks. In order to avoid alarm from
unused function blocks, congure
RESOURCE2.FD_EXTENDC_MAP_n
(n: 1 to 3) parameter.
Sensor/Actuator out of range Check specication Check specication of sensor and
actuator. Or process conditions may be
temporarily non-conforming.
Out of operating limit Check environment Check environment specication
of sensor and actuator. Or process
environment may be temporarily non-
conforming.
Temporal decrease of value quality Check process or peripherals Check process and peripherals
conditions.
Deterioration estimated by Time Based
Maintenance
Check deterioration Check if maintenance is required.
Deterioration estimated by Condition
Based Maintenance
Check deterioration Check if maintenance is required.
Optional function conguration error Check optional conguration Check conguration of optional
functions.
Alarm related information Conrm information Check the alarm related information.
Process alarm Check process Check process conditions.