Manual
<9. In-Process Operation>
9-3
IM 01S01C01-01EN
Table 9.2 Field Diagnostic Alert
Indication of FD_*_ACTIVE Indication of FD_RECOMMEN_ACT Solution
Electronics failure Repair electronics Replace electrical parts e.g. amplier.
Or contact sales ofce or service
center.
Sensor/Actuator failure Repair Sensor/Actuator Replace mechanics e.g. sensor or
actuator. Or contact sales ofce or
service center.
Potential failure Investigate failure Perform reconguration, cleaning,
wiring/connector or electrical board
check.
If alarm still persists, contact sales
ofce or service center.
Backup function in operation Repair primary side Repair primary sensor before backup
sensor fails.
Firmware update error Retry updating rmware Retry rmware update. Check cause of
the failure if alarm persists.
Communication conguration error Congure communication correctly Correct conguration of
communication.
Non-operating-state Wait for a while Wait for a while. Check cause of the
failure if alarm persists.
Calibration warning Check calibration Investigate cause of failure and
recalibrate device.
Device conguration error Congure device correctly Correct conguration relating to sensor
or actuator.
Function restricted Conrm the state Check if this is right state.
Simulation mode Conrm the state Check if this is right state.
Manual mode Conrm the state Check if this is right state.
Function Block notice Check Function Block status Check conditions of function
blocks. In order to avoid alarm from
unused function blocks, congure
RESOURCE2.FD_EXTENDC_MAP_n
(n: 1 to 3) parameter.
Sensor/Actuator out of range Check specication Check specication of sensor and
actuator. Or process conditions may be
temporarily non-conforming.
Out of operating limit Check environment Check environment specication
of sensor and actuator. Or process
environment may be temporarily non-
conforming.
Temporal decrease of value quality Check process or peripherals Check process and peripherals
conditions.
Deterioration estimated by Time Based
Maintenance
Check deterioration Check if maintenance is required.
Deterioration estimated by Condition
Based Maintenance
Check deterioration Check if maintenance is required.
Optional function conguration error Check optional conguration Check conguration of optional
functions.
Alarm related information Conrm information Check the alarm related information.
Process alarm Check process Check process conditions.