Manual

<2. Handling Cautions>
2-14
IM 01S01C01-01EN
b. IECEx Intrinsically Safe Type
Caution for IECEx Intrinsically safe type.
Note 1. FVX110 Fieldbus Segment Indicator with
optional code /SS25 are applicable for use
in hazardous locations:
No. IECEx DEK 11.0004 X
Applicable Standard:
IEC60079-0:2007, IEC60079-11:2006,
IEC60079-26:2006, IEC60079-27:2008
Note 2. Ratings
[Ex ia IIB/IIC T4 Ga]
Type of Protection: II1G Ex ia IIB/IIC T4 Ga
Ambient Temperature: –40* to 60ºC
* –15ºC when O-ring material is Fluoro-rubber.
Degree of Protection of the Enclosure:
IP66 and IP67
When combined with Trapezoidal output
characteristic FISCO model
IIC or IIB barrier
[Supply/Output circuit (terminals + and)]
Ui = 17.5 V, Ii = 500 mA, Pi = 5.5 W,
Ci = 3.52 nF, Li = 0
When combined with Linear characteristic
barrier
[Supply/Output circuit (terminals + and)]
Ui = 24.0 V, Ii = 250 mA, Pi = 1.2 W,
Ci = 3.52 nF, Li = 0
[Ex ic IIC T4 Gc]
Type of Protection: II3G Ex ic IIC T4 Gc
Ambient Temperature: –40* to 60ºC
* –15ºC when O-ring material is Fluoro-rubber.
Degree of Protection of the Enclosure:
IP66 and IP67
[Supply/Output circuit (terminals + and –)]
Ui = 32.0 V, Ci = 3.52 nF, Li = 0
Note 3. Installation
In any safety barrier used output current
must be limited by a resistor 'R' such that
Io=Uo/R.
The safety barrier must be IECEx certied.
Input voltage of the safety barrier must be
less than 250 Vrms/Vdc.
The instrument modication or parts
replacement by other than authorized
representative of Yokogawa Electric
Corporation and will void IECEx Intrinsically
safe certication.
Non-Hazardous Location
Hazardous Location
F0214.ai
Terminator
Safety Barrier
Field Instruments
Indicator
Field Instruments
+
+
+
Terminator
+
+
[Intrinsically safe apparatus level of protection “ia”]
F0215.ai
Terminator
General Porpose
Equipment
Terminator
+
+
[Intrinsically safe apparatus level of protection “ic”]
Non-Hazardous Location
Hazardous Location
Field Instruments
Indicator
Field Instruments
+
+
+