Manual

<Appendix 3. Input Selector (IS) Block>
A3-15
IM 01S01C01-01EN
Relative
Index
Index
IS1
Index
IS2
Parameter
Write
Mode
Valid Range
Initial
Value
View
Description / Remarks
1 2 3 4
14 17014 17114 IN_4 0 5 5 Input 4
15 17015 17115 DISABLE_1 0, 1 0 2 2 Selector switch to disable input 1 from being
selected.
16 17016 17116 DISABLE_2 0, 1 0 2 2 Selector switch to disable input 2 from being
selected.
17 17017 17117 DISABLE_3 0, 1 0 2 2 Selector switch to disable input 3 from being
selected.
18 17018 17118 DISABLE_4 0, 1 0 2 2 Selector switch to disable input 4 from being
selected.
19 17019 17119 SELECT_
TYPE
1-6 0 1 Species the input selection algorithm.
20 17020 17120 MIN_GOOD 0-8 0 1 Parameter specifying the minimum required
number of inputs with “good” status If the
number of inputs with “good” status is
less than the value of MIN_GOOD, input
selection is canceled.
21 17021 17121 SELECTED 0-8 0 2 2 Indicates the number of the selected input.
However, it indicates the number of inputs
used to calculate the average if SELECT_
TYPE = Average.
If no input is selectable or if there are
multiple inputs, it becomes0” (none).
22 17022 17122 OP_
SELECT
0-8 0 2 2 A parameter to forcibly employ the input of a
selected number (Operator-settable).
23 17023 17123 UPDATE_
EVT
- - Indicates event information if an update
event (setting change) occurs.
24 17024 17124 BLOCK_
ALM
- - Indicates alarm information if a block alarm
occurs.
25 17025
17125 IN_5 0 5 5 Input 5
26 17026 17126 IN_6 0 5 5 Input 6
27 17027 17127 IN_7 0 5 5 Input 7
28 17028 17128 IN_8 0 5 5 Input 8
29 17029 17129 DISABLE_5 0, 1 0 2 2 Selector switch to disable input 5 from being
selected.
30 17030 17130 DISABLE_6 0, 1 0 2 2 Selector switch to disable input 6 from being
selected.
31 17031 17131 DISABLE_7 0, 1 0 2 2 Selector switch to disable input 7 from being
selected.
32 17032 17132 DISABLE_8 0, 1 0 2 2 Selector switch to disable input 8 from being
selected.