Operation Manual

<5. Operational Flowchart>
5-8
IM 01C25R51-01E
(B) Conguration with existing conguration le (dns le)
Step FieldMate Menu
DYF(SoftDL) F
OUNDATION fieldbus DTM
Layer1 Layer2 Layer3
DYFMVTool
Main Window
Procedure
"Online Parameter" is opened.
Load the *.dns file 2)
- "User Flow Parameters"
- "Device Flow Parameters"
- "Device General Parameters"
Edit "Device General Parameters"
and Apply to "Offline Database".
Confirm the compensation
calculation by input simulation for
flow rate, temperature and
pressure.
Download "Device Flow
Parameters" and "Device General
Parameters".
Goes offline.
1
Start DTM
Open "DNS"
file and
download
parameters to
the device
Confirm flow
configuration
2
3
File
Assigned DTM
Device
Load from
file...
Parameter
Download to
device 1)
Online
Parameter
Disconnect
Device
F0506E.ai
1) Executing‘Downloadtodevice’willwriteboth“DeviceFlowParameters”and“DeviceGeneralParameters”intothe
device. Before executing ‘Download to device’, execute ‘Upload from device’, so as to make General Parameters of the
deviceintheofinedatabasesynchronizedwiththedevice.
*:UserFlowParametersconsistofuidinformationandoperatingcondition.
2) TemperatureunitandpressureunitinARBlockarenotconguredinFlowCongurationWizardDetailCompensation
Mode.
TheseparametersmustbesetmanuallyinARBlockofineparameter.