Operation Manual
    <5.  Operational Flowchart>
5-3
IM 01C25R51-01E
(B)  Congure with existing conguration le (dns/dfs le)
Step FieldMate Menu
EJX910 HART / F
OUNDATION fieldbus DTM
Layer1 Layer2 Layer3
EJXMVTool
Main Window
Procedure
"Online Parameter" is opened
Load the *.dns / dfs file
 - "User Flow Parameters"
 - "Device Flow Parameters"
 - "Device General Parameters"
Edit "Device General Parameters"
and Apply to "Offline Database".
Check the flow coefficient
The value is saved in a log file:
"FlowCoeffLog"
Download "Device Flow
Parameters" and "Device General
Parameters"
Goes offline
1
Start DTM
Open
 "DNS/DFS"
file and
download
parameters to
the device
Confirm flow
coefficient
2
3
File
Assigned DTM
Device
Load from
file...
Additional
Functions
Download to
device 1)
Obtain Flow
Coefficient
Disconnect
Device
F0502E.ai
1) Executing‘Downloadtodevice’willwriteboth“DeviceFlowParameters”and“DeviceGeneralParameters”into
thedevice.Beforeexecuting‘Downloadtodevice’,execute‘Uploadfromdevice’,soastomake“DeviceGeneral
Parameters”intheofinedatabasesynchronizedwiththedevice.
 Downloaddatatothedevicedoesnotinclude“UserFlowParameters”.










