Operation Manual
<Appendix B. Device Information>
B-9
IM 01C25R51-01E
Step 3 Check the alarm in AR Block
ConrmthatthefollowingalarmsarenotdisplayedinDiagnosticListoftheDeviceStatusscreen.
If any alarm is displayed for AR Block, take the appropriate measure by referring to the table
below.
Table B3.1 Alarm list of AR Block for ow conguration
Alarm No. Alarm Label Counter Measure
AL-85 AR Not Scheduled Make a schedule of AR Block
AL-86 AR Range Conf. Err C
hangethevalueasARRangeHigh(AR.RANGE_HI)islarger
thanARRangeLow(AR.RANGE_LO)
AL-87 AR Temp. IN Over Range T
hiscaseisoutofspecication.RefertoIM01F06F00-01Eor
Check the engineering setting or AR Temperature Unit
(AR.AR_TEMPERATURE_UNIT)
AL-88 AR Press IN Over Range T
hiscaseisoutofspecication.RefertoIM01F06F00-01Eor
ChecktheengineeringsettingorARPressureUnit(AR.AR_
PRESSURE_UNIT)andARBiasInput2(AR.BIAS_IN_2)
AL-89 AR Flow IN NotConnected C
onnectthevolumetricowdataintoARInput(AR.IN)
AL-90 AR Temp. IN NotConnected C
onnectthetemperaturedataintoARInput1(AR.IN_1)
AL-91 AR Press IN NotConnected C
onnectthepressuredataintoARInput2(AR.IN_2)
AL-92 AR Comp. Coef. Conf. Err E
xecute“FlowCongurationWizard”againanddownloadtothe
device.
AL-93 AR Output Unit Conf. Err Refer to IM 01F06F00-01E or Check the AR Output Range.Units
I
ndex(AR.OUT_RANGE.UnitIndex)andARArithmeticType
(AR.ARITH_TYPE)
NOTE
AsfordevicealarmsotherthanARBlock,refertoInstructionManual"ModelDYVortex
Flowmeter,ModelDYAVortexFlowConverter,andFieldbusCommunicationType"(IM
01F06F00-01E).