Operation Manual

<Appendix B. Device Information>
B-9
IM 01C25R51-01E
Step 3 Check the alarm in AR Block
ConrmthatthefollowingalarmsarenotdisplayedinDiagnosticListoftheDeviceStatusscreen.
If any alarm is displayed for AR Block, take the appropriate measure by referring to the table
below.
Table B3.1 Alarm list of AR Block for ow conguration
Alarm No. Alarm Label Counter Measure
AL-85 AR Not Scheduled Make a schedule of AR Block
AL-86 AR Range Conf. Err C
hangethevalueasARRangeHigh(AR.RANGE_HI)islarger
thanARRangeLow(AR.RANGE_LO)
AL-87 AR Temp. IN Over Range T
hiscaseisoutofspecication.RefertoIM01F06F00-01Eor
Check the engineering setting or AR Temperature Unit
(AR.AR_TEMPERATURE_UNIT)
AL-88 AR Press IN Over Range T
hiscaseisoutofspecication.RefertoIM01F06F00-01Eor
ChecktheengineeringsettingorARPressureUnit(AR.AR_
PRESSURE_UNIT)andARBiasInput2(AR.BIAS_IN_2)
AL-89 AR Flow IN NotConnected C
onnectthevolumetricowdataintoARInput(AR.IN)
AL-90 AR Temp. IN NotConnected C
onnectthetemperaturedataintoARInput1(AR.IN_1)
AL-91 AR Press IN NotConnected C
onnectthepressuredataintoARInput2(AR.IN_2)
AL-92 AR Comp. Coef. Conf. Err E
xecute“FlowCongurationWizard”againanddownloadtothe
device.
AL-93 AR Output Unit Conf. Err Refer to IM 01F06F00-01E or Check the AR Output Range.Units
I
ndex(AR.OUT_RANGE.UnitIndex)andARArithmeticType
(AR.ARITH_TYPE)
NOTE
AsfordevicealarmsotherthanARBlock,refertoInstructionManual"ModelDYVortex
Flowmeter,ModelDYAVortexFlowConverter,andFieldbusCommunicationType"(IM
01F06F00-01E).