Operation Manual
<Appendix B. Device Information>
B-8
IM 01C25R51-01E
B-3 How to Check digitalYEWFLO AR Block
Alarm
ConrmARBlockfunctionscorrectlybyfollowingtheproceduresbelow.
Step 1 Open Online Parameter in Device DTM
Start Device DTM to display the Online Parameter screen.
(
[Device]→[Parameter]→[OnlineParameter])
IMPORTANT
TurnonthealarmoutputofARBlockatTB:ALARM_PERFORM.
Default setting for the alarm output of AR Block is off.
(
OnlineParameter:[TransducerBlock]→[Alerts])
Step 2 Open the Device Status screen
Display the alarm of AR Block in Diagnostic List of the Device Status screen.
(
[OnlineParameter]→[DeviceStatus]→[DiagnosticList])
NOTE
ThealarminformationonARBlockappearsunder“Others”ofDiagnosticList.
Figure B3.1 Device Status screen