Operation Manual
<Appendix B. Device Information>
B-6
IM 01C25R51-01E
Step 5 Set function block connection information
Double-click"FunctionBlockApplication"ontheleftofthescreentodisplay"FunctionBlock
Application".
C
lick"WiringTool"onthemenubartoconnecttheblocksasshowninTableB2.3.
Table B2.3 Function blocks for wiring
Value Device Function Block Device Function Block
(1) V
olumetricFlowRate
(Qv)
digitalYEWFLO AI3 Block
OUT
digitalYEWFLO AR Block
IN
(2) Temperature Temperature Transmitter
(Yokogawa YTA320)
AI1 Block
OUT
digitalYEWFLO AR Block
IN_1
(3) Pressure Pressure Transmitter
(Yokogawa EJX510A)
AI1 Block
OUT
digitalYEWFLO AR Block
IN_2
FB0207E.ai
Function Block
Application
(1)
(2)
(3)
Wiring Tool
Figure B2.7 How to congure the function block connection
Step 6 Download function block scheduling and connection information
Write the function block scheduling and connection information in the segment where the device
exists after completing the setting.
<
Menu:[Congure]→[DownloadConguration]>
Figure B2.8 Before “Download Conguration”