Operation Manual
<7. Operation of EJXMVTool>
7-22
IM 01C25R51-01E
7.3 Obtain Flow Coefcient
Clickthe[Device]→[AdditionalFunctions]→[ObtainFlowCofcient]
Figure 7.22 Obtain Flow Coefcient
Theowcoefcientcanbeobtainedfromthetransmitter(inputselection:sensordataor
simulateddata).Theaboveowcoefcientwindowisdisplayedwhensensordataisselected.
Executeowsimulationforconrmationofconguredowparameters.Inputdifferential
pressure,staticpressure(absolue)andtemperaturevalueandconrmthatdesiredowis
obtained.
When the simulation is executed, it is necessary to connect RTD or mock resistance (about
1
00Ω)tothetransmitter.
Onceselecting“simulatedvalue”andpressthe[Execute]button,thetransmitteristransferred
to simulation mode. The transmitter will remain in the simulation mode for approximately 10
minutes and automatically return to normal mode. (Regarding the simulation duration time, refer
t
oUser’sManualIM01C25R02-01E“EJX910AandEJX930AMultivariableTransmitterHART
CommunicationType”andIM01C25R03-01E“EJX910AandEJX930AFieldbusCommunication
Type”)
P
ress[Simulationoffandclose]buttonifyouwishtonishthesimulationmodeimmediately.