Manual

<6 OPERATION>
6-37
IM 01R01A11-01EN
2)-2 When Verication Tool is in “ofinemode:
Read the value of parameter “Velocity Check” manually. Refer to Table 6.3.11. And enter
the value in “cell (2)in Figure 6.3.15 manually.
Table 6.3.11 AXF Parameter Settings of Converter Check
HART Parameter (DD)
Parameter of
AXF Display
Velocity Check Device setup Detailed Setup Basic Setup →Velocity Check C44
3) Measure the output accuracy at the preferred setting (0%, 25%, 50%, 75%, or 100%). After
setting the value, let the AM012 stabilize at least for 1 minute.
For operation procedure, follow User’s Manual FY2-XJAM012-40-2E.
4) Enter the measured value.
4)-1 When Verication Tool is in “onlinemode:
Click “Read (5)in Figure 6.3.15. The value of instantaneous ow rate is entered automati-
cally.
4)-2 When Verication Tool is in “ofinemode:
Read the value of parameter “PV” or “PV %rngemanually. Refer to Table 6.3.12, and
convert the value inm/sunit.
Enter the calculated value in “cell (4)” in Figure 6.3.15 manually.
Table 6.3.12 AXF Measured Value of “ConverterCheck
HART Parameter (DD)
Parameter of
AXF Display
PV
Process Variables PV
or
Device Status Process Variable PV
A20
PV %rnge
Process Variables PV %rnge
or
Device Status Process Variable PV %rnge
A10
5) “Error (%)” is calculated automatically.
6) “Result” is displayed automatically after lling in all elds.
F060318.ai
Figure 6.3.18 “Converter” Result
7) Set the AXF parameters back to their original values manually.