<6 OPERATION>
6-35
IM 01R01A11-01EN
6.3.3 Converter
WARNING
Follow User’s Manual FY2-XJAM012-40-2E for correct operation and safe handling.
This item checks the accuracy of the AXF converter with Magnetic Flowmeter Calibrator AM012.
1 2 3
5
4
F060315.ai
Figure 6.3.15 “Converter” Screen
Table 6.3.9 Converter
Item
No.
Item Name Description
1 Connection diagram
Shows the connection diagram on another screen. The diagram is (A) or
(B) in Figure 6.3.16 depending on the case.
2 Span
Shows the Span of the converter.
This eld can be edited.
3 Read Span
Reads the Span of the converter. Press “Read Span”.
(Only when Verication Tool is online to AXF)
4 Measured (m/s)
Shows the measured value.
This eld can be edited.
5 Read
Reads the measured value. PressRead”.
(Only when Verication Tool is online to AXF)
SB
BA
SA
C
AL–AL+COMSO2+SO1+I+ I–
CUR OUT STATUS OUT ALARM OUT SIGNAL
COMSI2+SI1+
EX2EX1
L/+N/–
POWER SUPPLY EXCITER
P–P+
PULSE OUT STATUS IN
(Shield) (White) (Black)
(Shield)
(White)
(Black)
AXFA11
AM012
F060316-A.ai
(Shield)
(White)
(Black)
(Shield)
(White)
(Black)
N /
L /
+
SA
SB
+
+
+
AM012
Junction Box Terminal
F060316-B.ai
(A) AXFA11 (B) AXFA14 or AXF Integral Flowmeter
Figure 6.3.16 “Converter” Connection Diagram