Manual

<6 OPERATION>
6-27
IM 01R01A11-01EN
1) Wire AXF and CA150 Handy Calibrator or similar as shown in Figure 6.3.3.
2) Set a current value to output.
2)-1 When Veri cation Tool is in “online” mode:
Select 4 mA, 12 mA, or 20 mA in “Output Selection” and click Output”.
F060304.ai
Figure 6.3.4 “Output Selection” in “Current Output”
2)-2 When Veri cation Tool is in “of inemode:
Set the AXF HART parameter “Loop testto the preferred value.
Table 6.3.3 Parameter Setting of “Current Output”
HART Parameter (DD)
Parameter of
AXF Display
Setting Value
Loop test Device Setup Diag/Service Output TestLoop test -
4 mA
20 mA
Other (12 mA)
3) Measure the current output value by using CA150 Handy Calibrator or similar for each set-
ting value.
4) Enter the measured current value in eachMesured(mA)” manually. “Error(%)” is calculated
automatically.
F060305.ai
Figure 6.3.5 “Current Output” Result
5) End processing
5)-1 When Veri cation Tool is in “online” mode:
Click “Exit” in “Output Selection”. “Resultis displayed automatically after lling in all elds.
5)-2 When Veri cation Tool is in “of inemode:
“Result” is displayed after lling in all elds.