Owner manual
29
IM 12B07C05-01E
5
MENU STRUCTURECOMMISSIONING
mA2 similar structure to mA1
Menu Parameter Default Range
values min. max.
mA1 (control) Expire time 0.0 sec. 0 sec. 1800 sec.
mA1 (output) Damping time 0.0 sec. 0 sec. 3600 sec.
mA1(simulate) Simulationperc. 50% 0% 100%
P(ID)-controlmA1 Setpoint 7pH -inf +inf
P(ID)-controlmA2 Setpoint 25ºC/ºF -inf +inf
P(ID)-control mA1 Range 1.00 pH -inf +inf
P(ID)-controlmA2 Range 10ºC/ºF -inf +inf
P-controlmA1 ManualReset 0% 0% 100%
PI(D)-control mA1 I-time 3600 sec. 1 sec. 3600 sec.
P(I)D-control mA1 D-time 0 sec. 0 sec. 60 sec.
LinearmA1 0%Value 0pH -inf +inf
LinearmA2 0ºC/ºF -inf +inf
LinearmA1 100%value 14pH -inf +inf
LinearmA2 100ºC/ºF -inf +inf
Table Table mA1 see appendix 1 -2 pH 16 pH