User’s Manual Model ISC202G [Style: S2], ISC202S [Style: S3] 2-wire Inductive Conductivity Transmitter IM 12D06A03-01E IM 12D06A03-01E 7th Edition
TABLE OF CONTENTS PREFACE 1. Introduction And General Description ............................................................. 1-1 1-1. Instrument check ............................................................................................ 1-1 1-2. Application ...................................................................................................... 1-3 2. GENERAL SPECIFICATIONS ............................................................................. 2-1 2-1. Specifications..........
5. Parameter setting ............................................................................................... 5-1 5-1. Maintenance mode ......................................................................................... 5-1 5-1-1. 5-1-2. 5-1-3. 5-1-4. 5-1-5. Introduction ......................................................................................................................5-1 Manual calibration to determine the cell constant (C.C.) ...............................................
12. APPENDIX 2....................................................................................................... 2-1 12-1. Preface ........................................................................................................ 2-1 12-2. Wiring diagrams............................................................................................. 2-1 12-3. Peripheral products........................................................................................ 2-2 12-3-1.
PREFACE DANGER Notice • This manual should be passed on to the end user. Electric discharge • The contents of this manual are subject to The EXA analyzer contains devices that can be change without prior notice. damaged by electrostatic discharge. When servicing • The contents of this manual shall not be this equipment, please observe proper procedures reproduced or copied, in part or in whole, to prevent such damage. Replacement components without permission. should be shipped in conductive packaging.
The following safety symbols are used on the product as well as in this manual. DANGER DANGER This symbol indicates that an operator must follow the instructions laid out in this manual in order to avoid the risks, for the human body, of injury, electric shock, or fatalities. The manual describes what special care the operator must take to avoid such risks.
ATEX Documentation This procedure is only applicable to the countries in European Union. GB All instruction manuals for ATEX Ex related products are available in English, German and French. Should you require Ex related instructions in your local language, you are to contact your nearest Yokogawa office or representative. DK Alle brugervejledninger for produkter relateret til ATEX Ex er tilgængelige på engelsk, tysk og fransk.
SK PL CZ SLO LT H BG LV EST RO M IM 12D06A03-01E
Introduction 1-1 1. INTRODUCTION AND GENERAL DESCRIPTION The Yokogawa EXA 202 is a 2-wire transmitter designed for industrial process monitoring, measurement and control applications. This user’s manual contains the information needed to install, set up, operate and maintain the unit correctly. This manual also includes a basic troubleshooting guide to answer typical user questions. Yokogawa can not be responsible for the performance of the EXA transmitter if these instructions are not followed. 1-1.
1-2 Introduction ISC TRANSMITTER ISC TRANSMITTER MODEL SUFFIX MODEL SUFFIX ISC202S-F 17.5VDC or 24VDC 17.5VDC or 24VDC /380mA/5.32W /250mA/1.2W /380mA/5.32W OUTPUT PROFIBUS-PA Li=0 μH, Ci=220pF AMB.TEMP. -10 55°C AMB.TEMP. -10 55°C STYLE No. ISC TRANSMITTER MODEL SUFFIX R LR81741 C MODEL SUFFIX ISC202S-F/-P FNICO field device ISC202S-D II 3 G SUPPLY OUTPUT AMB.TEMP. SUPPLY OUTPUT 9 TO 32VDC FF-TYPE 113 -10 55°C AMB.TEMP. STYLE No. Figure 1-2.
Introduction 1-3 1-2. Application The EXA transmitter is intended to be used for continuous on-line measurement in industrial installations. The unit combines simple operation and microprocessor-based performance with advanced selfdiagnostics and enhanced communications capability to meet the most advanced requirements. The measurement can be used as part of an automated process control system.
1-4 Introduction IM 12D06A03-01E
Specifications 2-1 2. GENERAL SPECIFICATIONS mA F) Transmission signal: - General Isolated output of 4-20 mA DC.Burn up (21 mA) or Burn A) Input specifications down (3.6 mA when HART® :One inductive conductivity sensor and one or distributor comm. is nontemperature sensor. Compatible with the used, 3.9 mA when HART® ISC40 series with integrated temperature senor distributor comm. is used) sor. ISC202S: use with ISC40S or pulse of 21 mA to signal failure.
2-2 Specifications Load Resistance (Ω) 800 P) Housing: - Material : 775 600 425 400 - Color : Case : Possible 200 0 12 17 16 20 24 28 32 31.5 V Voltage (V) Fig.2-2 Supply voltage/ load diagram for the ISC202S J) Temperature compensation: - Sensor types: Pt1000Ω or 30kΩ NTC - Automatic: -20 to 140 ºC (0 to 280 ºF) - Algorithm: selectable as mentioned below NaCl according to IEC 60746-3 tables. Two T.C. setting possible between 0.00 to 3.50 %/°C Matrix: user selectable/ configurable.
Specifications 2-3 V) Explosionproof type Refer to Control Drawings. mA Item Factory Mutual (FM) Description FM Intrinsically safe Approval Applicable standard: FM3600, FM3610, FM3810 Intrinsically Safe for Class I, Division 1, Groups ABCD Class I, Zone 0, AEx ia IIC Temp. Class: T4, Amb. Temp.: -10 to 55°C Intrinsically Safe Apparatus Parameters Vmax=31.5 V, Imax=100 mA, Pmax=1.
2-4 Specifications mA NEPSI Certification (ISC202S-K) NEPSI Intrinsically Safe Type Cert No. GYJ081158X • Applicable Standard: GB3836.1-2000, GB3836.4-2000 • Type of Protection and Marking Code: Ex ia IIC T4/T6 • Ambient Temperature : T6; –10 to 40°C, T4; –10 to 55°C Note 1 Entity Parameters • Intrinsically safe input parameters (terminal + and -): Maximum Input Voltage (Ui) = 31.5 V Maximum Input Current (Ii) = 100 mA Maximum Input Power (Pi) = 1.
Specifications 2-5 PROFIBUS-PA communications L. Hardware: F-BUS interfaces from National A. Input signal: Digital Instruments (AT-FBUS, PCMIAB. Supply voltage: 9 to 32 V DC FBUS) C. Operating current: 26.0 mA M. Other control systems: D. Operating values: According to IEC 1158-2 YOKOGAWA PRM, DTM E. Bus connection : Fieldbus interface base on IEC1158-2 according to FISCOModel F. Power supply: Power supply is achieved dependant on the application by means of segment coupler G.
2-6 Specifications 2-2. Model and suffix codes 1.
Specifications 2-7 2-3. Control Drawing ISC202S mA HART® Specification (IECEx). Intrinsically safe design IEC Ex standard Ex ia IIC : T4 for ambient temp. < 55°C T6 for ambient temp. < 40°C C ertificate nr. IEC Ex KEM 06.0054X ISC 202S (Inductive C onductivity-transmitter) Ex ia or ib C ertified safety barrier or pow er w ith R int=300 : (HAR T compatible) 24 volts D C N ominal Supply V oltage. + + _ ISC 40S Sensor term inals 11-17 _ U o = 31.
2-8 Specifications 2-4. Control Drawing ISC202S mA HART® Specification (ATEX) Intrinsically safe design CEN ELEC standard EEx ia IIC: T4 for ambient temp. < 55°C T6 for ambient temp. < 40°C C ertificate nr. KEM A 06ATEX 0222 X ISC 202S (Indutive Conductivity transmitter) EEx ia or ib Certified safety barrier or pow er with Rint=300 : (HART compatible) 24 volts D C N ominal Supply Voltage.
Specifications 2-9 2-5. Control Drawing ISC202S mA HART® Specification (FM Intrinsically safe design) Intrinsically safe design FM Class I, Div.1, Group ABCD, T4 for ambient temp. < 55°C T6 for ambient temp. < 40°C ISC202S transmitter FM Approved safety barrier or power supply with Rint = 300 : (HART compatible) 24 volts DC Nominal Supply Voltage. + + _ - G ISC40S Sensor For electrical data: see text below. terminals 11-17 Max. cablelength: 60 mtr. Cable dia. : 3…12 mm.
2-10 Specifications 2-6. Control Drawing ISC202S mA HART® Specification (FM Non-incendive design) Nonincendive design FM Class I, Div.2, Group ABCD, ISC202S T4 T6 for ambient temp. < 55°C for ambient temp. < 40°C FM Approved power supply Voc ≤ 31.5 V DC transmitter + + _ - G ISC40S Sensor terminals 11 -17 Max. cablelength: 60 Cable dia. : 3…12 mm. For electrical data: see text below. mtr.
Specifications 2-11 2-7. Control Drawing of ISC202S mA HART® Specification (CSA) Intrinsically safe design C SA Ex ia C lass I, D iv.1, G roup A BC D , T4 for ambient temp. < 55°C T6 for ambient temp. < 40°C C SA certified safety barrier or pow er supply w ith R int=300 : (HA R T compatible) ISC 202S transmitter 24 volts D C N ominal Supply V oltage. + + _ G Fo r electrical data: see text belo w .
2-12 Specifications 2-8. Control Drawing of ISC202S FF/PB Specification (IECEx) Ex ia IIC T4 for ambient temp. d 55 qC Ui = 24 V or Ui = 17,5 V Ii = 250 mA Ii = 380 mA Pi = 1,2 W Pi = 5,32 W ISC202S-F or ISC202S-P + Safe area Apparatus + - I.S. interface Sensor Connections - I.S. certified Term inator I.S. certified Term inator + - Transm itter Safe area + - Transm itter Zone 0 or 1 Hazardous area x x Sensor(s) are of a passive type to be regarded as 'simple apparatus'.
Specifications 2-13 2-9. Control Drawing of ISC202S FF/PB Specification (ATEX) Ex ia IIC T4 for ambient temp. d 55 qC Ui = 24 V or Ui = 17,5 V Ii = 250 mA Ii = 380 mA Pi = 1,2 W Pi = 5,32 W ISC202S-F or ISC202S-P + Safe area Apparatus + - I.S. interface Sensor Connections - I.S. certified Terminator I.S. certified Terminator + - Transmitter Safe area + - Transmitter Zone 0 or 1 Hazardous area x Sensor(s) are of a passive type to be regarded as 'simple apparatus'.
2-14 Specifications 2-10. Control Drawing of ISC202S FF/PB Specification (FM Intrinsically safe Entity) FM Class I, DIV. 1, Group ABCD T4 for ambient temp. d 55 qC Sensor Connections Max. cablelength: 60 mtr. Cable dia. : 3…12 mm. ISC202S-F or ISC202S-P + FM Approved barrier Voc (Vt) d 24 V Ioc (It) d 250 mA Poc (Pt) d 1.2 W Ca t 220pF+ Ccable La t 0 H + Lcable + - Sensor Connections - I.S. certified Terminator I.S.
Specifications 2-15 x The cable used to interconnect the devices needs to comply with the following parameters: Loop resistance R’: 15 … 150 Ω/km; Inductance per unit length L’: 0,4 … 1 mH/km Capacitance per unit length C’: 80 … 200 nF/km (C’ = C’ line/line + 0,5 C’ line/screen if both line are floating) (C’ = C’ line/line + C’ line/screen if the screen is connected to one line) Length of spur cable: max. 30 m Length of trunk cable: max. 1 km Length of splice : max.
2-16 Specifications 2-11. Control Drawing of ISC202S FF/PB Specification (FM Intrinsically safe FISCO) FM Class I, DIV. 1, Group ABCD T4 for ambient temp. d 55 qC Sensor Connections Max. cablelength: 60 mtr. Cable dia. : 3…12 mm. Sensor Connections ISC202S-F or ISC202S-P + FM Approved FISCO barrier Voc (Vt) d17,5 V Ioc (It) d380 mA Poc (Pt) d5,32 W + - - FM Approved Terminator R = 90..100Ω C = 0..2,2 μF FM Approved Terminator R = 90..100Ω C = 0..
Specifications 2-17 x In each I.S. Fieldbus segment only one active source, normally the FM Approved FISCO barrier, is allowed to provide the necessary power for the Fieldbus system. All other equipment connected to the bus cable has to be passive (not providing energy to the system), except to a leakage current of 50μA for each connected device. Seperately powered equipment needs a galvanic isolation to insure that the I.S. Fieldbus circuit remains passive.
2-18 Specifications 2-12. Control Drawing of ISC202S FF/PB Specification (FM Non-incendive Entity) FM Class I, DIV. 2, Group ABCD T4 for ambient temp. d 55 qC T6 for ambient temp. d 40 qC Sensor Connections Max. cablelength: 60 mtr. Cable dia.: 3…12 mm. Sensor Connections ISC202S-B or ISC202S-D + FM Approved Power Supply Voc d 32 VDC - FM Approved Terminator R = 90..100Ω C = 0..2,2 μF + - FM Approved Terminator R = 90..100Ω C = 0..
Specifications 2-19 2-13. Control Drawing of ISC202S FF/PB Specification (FM Non-incendive FNICO) FM Class I, DIV. 2, Group ABCD T4 for ambient temp. d 55 qC T6 for ambient temp. d 40 qC Sensor Connections Max. cablelength: 60 mtr. Cable dia.: 3…12 mm. Sensor Connections ISC202S-B or ISC202S-D FM Approved Power Supply Voc d 32 VDC + - + - FM Approved Terminator R = 90..100Ω C = 0..2,2 μF FM Approved Terminator R = 90..100Ω C = 0..
2-20 Specifications 2-14. Control Drawing of ISC202S FF/PB Specification (CSA) CSA Ex ia Class I, DIV. 1, Group ABCD T4 for ambient temp. d 55 qC Ui = 24 V Ii = 250 mA Pi = 1,2 W or Ui = 17,5 V Ii = 380 mA Pi = 5,32 W ISC202S-F or ISC202S-P + Safe area Apparatus + - I.S. interface Sensor Connections - I.S. certified Terminator I.S.
Installation and wiring 3-1 3. INSTALLATION AND WIRING 3-1. Installation and dimensions 3-1-1. Installation site The EXA transmitter is weatherproof and can be installed inside or outside. It should, however, be installed as close as possible to the sensor to avoid long cable runs between sensor and transmitter. In any case, the cable length should not exceed 60 mtr (200 feet).
3-2 Installation and wiring Unit: mm (inch) 18.5 (0.72) +1 0 +1 0 SPACING PANEL CUTOUT PANEL CUTOUT 3.5 (0.14) Unit: mm (inch) Fig. 3-2b. Panel mounting using two (2) self-tapping screws Pipe mounting (Vertical) 56 (2.20) Pipe mounting (Horizontal) 2-Ø6.5 (0.26) 200 (7.87) 4-Ø10 (0.4) 77 (3) 115 70 (4.5) (2.75) Nominal 50 A (O.D. Ø60.5 mm) (2 inch pipe) Figure 3-3. Wall and pipe mounting diagram Sensor cable glan Grounding terminal Figure 3-4.
Installation and wiring 3-3 to 2.5 mm (26 to 14 AWG). The glands will form a tight seal on cables with an outside diameter in the range of 6 to 12 mm (0.24 to 0.47 inches). mA COMPUTER HAND HELD COMMUNICATOR HOLD MODE FAIL YES N O ENT MEASURE CAL DISPLA Y HOLD MODE mA OUTPUT SUPPLY INPUT 2,5 or 10 m Supply mA CURRENT OUTPUT DISTRIBUTOR mA-Output Safety Barrier ISC202S only 0 12 100 SENSORS 180 RECORDER Figure 3-6. System configuration 3-3. Wiring of sensors 3-3-1.
3-4 Installation and wiring 3-4 Wiring of the power supply 3-4-1 General precautions WARNING First make sure that the DC-power supply is according the specifications given. DO NOT USE ALTERNATING CURRENT OR MAINS POWER SUPPLY! ! The cable leading to the distributor (power supply) or safety barrier transports power to an output signal from the transmitter. Use a two conductor shielded cable with a size of at least 1.25 mm2 and an outside diameter of 6 to 12 mm.
Installation and wiring 3-5 3-6. Other sensor systems To connect other sensor systems, follow the general pattern of the terminal connections as listed below: 11 and 12 : Always used for temperature compensation resistor input. 13 and 17 : Used for the secondary ‘collector’ coil. 15 and 16 : Used for the primary ‘drive’ coil. 14 : Overall screen Figure 3-8. Terminal identification label 3-6-1.
3-6 Installation and wiring Extension cable may be purchased in bulk quantities, cut to length. Then it is necessary to terminate the cable as shown below. Termination procedure for WF10 cable. 1. Slide 3 cm of heat shrink tube (9 x 1.5) over the cable end to be terminated. 2. Strip 9 cm of the outer (black) insulating material, taking care not to cut or damage internal cores. 3 cm heat shrink 9 cm remove insulation Fig. 3-10-1. 3.
Operation 4-1 4. OPERATION; DISPLAY FUNCTIONS AND SETTING 4-1. Operator interface This section provides an overview of the operation of the EXA operator interface. The basic procedures for obtaining access to the three levels of operation are described briefly. For a step-by-step guide to data entry, refer to the relevant section of this user’s manual. Figure 4-1 shows the EXA operator interface. LEVEL 1: Maintenance These functions are accessible by pushbutton through a flexible front cover window.
4-2 Operation Output hold flag Fail flag HOLD FAIL Menu pointer flags MODE Units Main display YES NO ENT MEASURE CAL DISPLAY HOLD OUTPUT SET HOLD TEMP SERVICE Commissioning function menu Message display YES NO MODE Key prompt flags Selection keys YES : Accept setting NO : Change setting Adjustment keys > : Choose digit to adjust ^ : Adjust digit ENT : Confirm change Commissioning mode access key ENT Measure/Maintenance mode key Broken line indicates area that can be seen through front cove
Operation 4-3 4-3. Setting passcodes 4-3-1. Passcode protection In Service Code 52, EXA users can set the passcode protection for each one of the three operating levels. This procedure should be completed after the initial commissioning (setup) of the instrument. The passcodes should then be recorded safely for future reference. When passcodes have been set, the following additional steps are introduced to the configuration and programming operations: Maintenance Press MODE key.
4-4 Operation 4-5. Display functions Display functions daigram is shown below. Display Functions μS / c m Actual cell constant YES NO NO μS/cm μS / c m Reference temperature MODE DISP.1 or DISP.
Parameter setting 5-1 5. PARAMETER SETTING 5-1. Maintenance mode 5-1-1. Introduction Standard operation of the EXA transmitter involves use of the Maintenance (or operating) mode to set up some of the parameters. Access to the maintenance mode is available via the six keys that can be pressed through the flexible window in the instrument front cover. Press the ‘MODE’ key once to enter this dialog mode.
5-2 Parameter setting 5-1-2. Manual calibration to determine the cell constant (C.C.) TO DISP.1 Enter the Conductivity value of the sample at reference temperature (IF HOLD ENABLED TO HOLD ELSE TO MEASURE.
Parameter setting 5-3 5-1-3. Second Line display. Referring to the first compensated conductivity. DISP.2 IF TEMP.2 = TEMP.
5-4 Parameter setting 5-1-4. Second Line display. Referring to the second compensated conductivity. 2nd Conductivity Value Compensation method for second conductivity value.
Parameter setting 5-5 mA 5-1-5. Manual activation of HOLD This option is only available if HOLD is enabled in Section 5-2.
5-6 Parameter setting 5-2. Commissioning mode In order to obtain peak performance from the EXA ISC202, you must set it up for each custom application. mA *OUTP mA *HOLD *TEMP.1, 2 *SERV : mA output is set as default to 0-1000 mS/cm. For enhanced resolution in more stable measuring processes, it may be desirable to select for example 0-100 μS/cm range. : The EXA ISC202 transmitter has the ability to ‘HOLD’ the output during maintenance periods.
Parameter setting 5-7 mA 5-2-1.
5-8 Parameter setting mA 5-2-2. HOLD * Here HOLD is enabled/disabled. When enabled: • The analyser’s output will be set to HOLD when entering Maintenance-, Commissioning- or Service menu. • Up on exiting one of the menus, the user is asked if HOLD should remain activated.
Parameter setting 5-9 5-2-3. Temperature compensation Why temperature compensation? The conductivity of a solution is very dependent on temperature. Typically for every 1 °C change in temperature the solution conductivity will change by approximately 2 %. The effect of temperature varies from one solution to another and is determined by several factors like solution composition, concentration and temperature range.
5-10 Parameter setting Calculation example Calculate the temperature co-efficient of a liquid from the following data. Conductivity 124.5 μS/cm at a liquid temperature of 18.0 °C and a conductivity 147.6 μS/cm at a liquid temperature of 31.0 °C. Substituting the data in the above formula gives the following result. α= 147.6 - 124.5 x 100% = 1.298%/ ºC 124.5(31.0 - 25) - 147.6(18.0 - 25) Set the temperature coefficient in the EXA transmitter. 2-C.
Parameter setting 5-11 5-2-4. Temperature compensation for first conductivity value (To *TEMP.
5-12 Parameter setting 5-2-5.
Parameter setting 5-13 5-3. Service Codes Don't set or input service code numbers other than the code numbers defined in this manual. Setting an undefined service code may make the transmitter malfunction. When an undefined service code is input by some accident, push the MODE key and escape from the service level. 5-3-1. Parameter specific functions Code 03 *C.C. Enter the factory calibrated cellconstant mentioned on the textplate or on the fixed cable. This avoids the need for calibration.
5-14 Parameter setting 5-3-3. Temperature compensation functions Code 20 *T.R.°C Choose a temperature to which the measured conductivity (or resistivity) value must be compensated. Normally 25°C is used, therefore this temperature is chosen as default value. Limitations for this setting are: -20 to 140 °C. If *T.UNIT in code 11 is set to °F, default value is 77°F and the limitations are 0 - 280°F. Code 21 *T.C.
Parameter setting 5-15 Code Display Function Temperature compensation functions Function detail 20 *T.R.°C Set reference temp. Use 21 *T.C.1 Set temp. coef. 1 Set temp. coef. 2 *MATRx Select matrix 24 *T1 °C (°F) Set temp. range 2.10 % per °C keys Adjust compensation factor 2.10 % if set to *T.C. in section 5-2-5. per °C keys Choose matrix if set to *MATRX keys H2SO4, 0 -100ºC, 0.5 - 5% 1 H2SO4, 0 -100ºC, 2.5 - 25% 2 HCl, 0 - 60ºC, 0.
5-16 Parameter setting mA 5-3-4. mA output functions Code 31 *OUTP.F For the ISC202 the output may be chosen as linear to input, or configured in a 21 point table to a particular linearization. Enable the table setup in code 31, and configure the table in code 35. Code 32 *BURN Diagnostic error messages can signal a problem by sending the output signals upscale or downscale (21 mA or 3.6 mA when HART or distributor comm. is non-used, 3.9 mA when HART or distributor comm. is used).
Parameter setting 5-17 Concentration Output function is done in de following order: • Set *OUTP.F. (Service Code 31) to table • Set the Concentration range in % (Service Code 55) • Set table values (%output and Conductivity values) in *TABLE (Service Code 35) mA Code Display mA Outputs 30 31 *OUTP.F Function 32 *BURN Burn function *TABLE *0% *5% *10% Output table for mA 33, 34 35 ... ...
5-18 Parameter setting 5-3-5. User interface Code 50 *RET. When Auto return is enabled, the transmitter reverts to the measuring mode from anywhere in the configuration menus, when no button is pressed during the set time interval of 10 minutes. Code 52 *PASS Passcodes can be set on any or all of the access levels, to restrict access to the instrument configuration. Code 53 *Err.05 to Error message configuration. Two different types of failure mode can be set. *Err.
Parameter setting 5-19 5-3-6. Communication setup mA Code 60 *COMM. *ADDR. The settings should be adjusted to suit the communicating device connected to the output. The communication can be set to HART® or to PH 201*B distribution (see Appendix 2). Select address 00 for point to point communication with 4-20mA transmission. Addresses 01 to 15 are used in multi-drop configuration (fixed 4mA output).
5-20 Parameter setting mA mA Code Display Communication 60 *COMM. 61 62 63-69 *ADDR. *HOUR *MINUT *SECND *YEAR *MONTH *DAY *ERASE Code Display General 70 *LOAD 71-79 IM 12D06A03-01E Function Function detail Communication Set HART® communication Set HART® communication Set communication PH 201*B Communication write enable Communication write protect Set address 00 to 15 Adjust to current date and time keys Network address Clock setup X off on on Y Z 0 1 2 Default values 1.
Calibration 6-1 6. CALIBRATION 6-1 When is calibration necessary? Calibration of conductivity instruments is normally not required, since Yokogawa delivers a wide range of sensors, which are factory calibrated traceable to NIST standards. The cell constant values are normally indicated on the top of the sensor or on the integral cable. These values directly can be entered in service code 03 (section 5-3-1). If the cell has been subjected to abrasion (erosion or coating) calibration may be necessary.
6-2 Calibration 6-2. Calibration procedure MODE MEASURE CAL DISPLAY HOLD YES NO MODE ENT Press the MODE key The legend CALIB appears, and the YES/NO key prompt flags flash Put the sensor in standard solution Press YES Set the value using the key Select the flashing digit with the key Increase it’s value by pressing the key When the correct value is displayed, press ENT to enter the change After briefly displaying WAIT, the CAL.
Maintenance 7-1 7. MAINTENANCE 7-1. Periodic maintenance for the EXA 202 transmitter The EXA transmitter requires very little periodic maintenance. The housing is sealed to IP65 (NEMA 4X) standards, and remains closed in normal operation. Users are required only to make sure the front window is kept clean in order to permit a clear view of the display and allow proper operation of the pushbuttons. If the window becomes soiled, clean it using a soft damp cloth or soft tissue.
Trouble shooting 8-1 8. TROUBLESHOOTING 8-1. Introduction The EXA ISC202 microprocessor based conductivity analyser continuously monitors the condition of all key components of the measuring system to ensure that measurement is dependable. If a fault is detected this is immediatly signalled. Errors are shown on the display with a code. Table shows the errors which can be detected and gives information to help locate the fault or identify the error.
Error messages 9-1 9.
Spare parts 10-1 10. SPARE PARTS See Customer Maintenance Parts List.
Appendix 1-1 11. APPENDIX 1 mA 11-1. User setting for non-linear output table (code 31, 35) Output signal value % mA % S/cm % S/cm Output 4-20 0 4.0 5 4.8 10 5.6 15 6.4 20 7.2 25 8.0 30 8.8 35 9.6 40 10.4 45 11.2 50 12.0 55 12.8 60 13.6 65 14.4 70 15.2 75 16.0 80 16.8 85 17.6 90 18.4 95 19.2 100 20.0 % S/cm 11-2. User entered matrix data (code 23 to 28) Medium: Code 23 Code 24 Code 25 Code 26 Code 27 Code 28 Temperature Solution 1 Solution 2 Solution 3 Solution 4 Solution 5 T1...
1-2 Appendix 11-3. Matrix data table (user selectable in code 22) Matrix, Solution 1. Sulfuric acid H2SO4 0.5 – 5 % Temp ( ºC) Data 1 Data 2 Data 3 Data 4 Data 5 1% 33.8 mS 47.0 mS 57.5 mS 63.7 mS 68.0 mS 5% 154.0 mS 218.0 mS 270.0 mS 307.0 mS 336.0 mS 1% 65 mS 91 mS 114 mS 135 mS 159 mS 2% 63.5 mS 92.3 mS 112.5 mS 126.0 mS 137.5 mS 10 % 292.0 mS 424.0 mS 534.0 mS 612.0 mS 673.0 mS 2% 125 mS 173 mS 217 mS 260 mS 301 mS 3% 95.0 mS 135.3 mS 166.0 mS 188.5 mS 206.0 mS 15 % 398.0 mS 590.0 mS 749.
Appendix 1-3 11-4. Configuration Checklist For ISC202 Primary choices Defaults Measurement 1st Temp. compensation 2nd Temp. compensation 2nd Line display Alternatives Conductivity NaCl in water NaCl in water Process temp. Fixed T.C., Matrix Fixed T.C., Matrix (inactive) 1st compensation method, Weight%, Output (mA), C.C., Ref. Temp.
1-4 Appendix mA 11-6. Device Description (DD) menu structure The Device Description (DD) is available from Yokogawa or the HART® foundation. An example is shown below of the ON LINE menu structure. This manual makes no attempt to explain the operation of the Hand Held Communicator (HHC). For detailed operating instructions, refer to the HHC instruction manual and the on-line help structure. Level 1 menu Level 2 menu Process variab. Process value Second process value Uncomp. process val.
Appendix 2-1 12. APPENDIX 2 12-1. Preface This appendix contains these items. 1. Method of wiring and parameter setting the following:. PH201G*B Dedicated Distributor BA2O Junction Terminal Box WF1OJ Extension Cable 2. Quick reference for parameter setting 3. Installation factor adjustment. To ensure that this measurement system can be operated safely and also exhibit its full performance, be sure to read this appendix before use.
2-2 Appendix 12-3. Peripheral products 12-3-1. PH201G*B Dedicated Distributor Model and suffix codes Model Suffix Code Option Code Power Supply Description Distributor PH201G -A1 100V AC -A2 220V AC Style B *B /TB Option Terminal for Power connection T2.2.2E.EPS Communication setup with PH201G (style B) distributor (service code 60) This communication is a one-way to PH201G (Style B) distributor, a power supplier for the EXA 202 transmitters.
Appendix 2-3 12-3-2. BA20 Junction Terminal Box Model and suffix codes Suffix code Model Option code Description Terminal box BA20 T1.3.5.eps External Dimensions and Wiring 160 100 142 160 142 33 4-Φ6.6 Mounting hole Inlet for extension cable (Φ21.5 hole) (36) Equivalent to DIN Pg13.5 cable gland (50) (60) (50) Ground terminal M4 Screw Inlet for detector cable (Φ21.5 hole) Equivalent to DIN Pg13.
2-4 Appendix 12-3-3. WF10J Extension Cable Model and suffix codes Model Suffix Option code code WF10J Cable end Cable length Description Extension cable -F Finished ends -05 -10 -20 -30 -40 5m 10 m 20 m 30 m 40 m T1.3.6.eps (Note) The maximum extension cable length is 50m including sensor cable length. External Dimensions and Wiring Terminal for BA20 terminal box Terminal for ISC202 inductive conductivity transmitter 11 12 11 12 13 13 17 17 Φ7.
Appendix 2-5 12-4. Quick reference for parameter setting Preparation for operation entails deciding maintenance-mode settings and measurement range setting-related issues. Service level (mode) settings are described in Sec. 5-3. Shipping-time measurement parameter setting defaults are shown in Table 12-1. In general there is no need to change these defaults. Table 12-1 Default values of parameters.
2-6 Appendix 12-4-1. Settings Performed in Maintenance Mode 12-4-1-1 Calibration with solution of known conductivity Refer to Sec. 6 for Calibration 1.
Appendix 2-7 12-4-2. Commissioning Mode Settings 12-4-2-1 Output Range Setting Refer to Sec. 5-2-1 1. What does output range setting involve? When linear output (linear relationship between conductivity and analog output) is selected, the measurement range corresponding to the 4 to 20 mA DC analog output range must be set. The default measurement range is 0 to 1,000 mS/cm. The display autoranges up to 1999 mS/cm. Zero suppression and non-linear output characteristic may be set (see Sec. 5-2). > > > 2.
2-8 Appendix 3. Examples While washing a reactor, HOLD is turned ON to prevent interference with control. When washing finishes, and a new batch starts, HOLD is turned OFF again and the sensor reverts to conductivity measurement. 4. Auto Return If AutoReturn functions are enabled, the instrument reverts to measurement mode after a preset time (10 min. by default) Refer to Sec. 5-3-5 User Interface. 12-4-2-3 Temperature Compensation Refer to Sec. 5-2-3 for details. 1.
Appendix 2-9 12-4-3. Actual Setting Examples WARNING Do not enter any Service Codes other than those specified in this document. If you enter a non-specified Service Code it may affect the program firmware or data, and adversely affect the operation of the instrument. This section provides representative key operation flowcharts. Displays like *SERVXX, where XX is a number, represent Service Codes. Refer to Sec. 5 for details. For other modes, refer to Sec. 6-1 and 6-2.
2-10 Appendix 12-4-3-1 Setting Output in terms of Concentration START Set Reference Temperature Set Measurement Range Method 1: Linear relationship between conductivity and concentration *OUTP Enter conductivities corresponding to 0% and 100% output conductivity concentration Method 2: Line-segment modeling of non-linear relationship between conductivity and concentration conductivity *SERV 31 select 1 *SERV 35 Enter conductivity values corresponding to concentration represented by output current conce
Appendix 2-11 Sample 1 NaCl concentration Meas. range 250-320 g/l Reference temp. Temp. compensation 60°C Use NaCl compensation (default) Concentration ― conductivity relationship is linear START Service Code 20 60°C OUTP 0% out -> 404 mS/cm 100% out -> 450 mS/cm (These conductivity values apply to reference temperature) Service Code 55 Select 1 0% out --> "25%" representing 250 g/l 100% out --> "32%" representing 320 g/l (g/l display not supported, so here using % instead. Also display is XX.
2-12 Appendix Sample 2 NaOH concentration Meas. range Reference temp. 0-10% 25°C Temp. compensation Use existing (temperature, concentration) matrix START Service Code 20 25°C (default) Service Code 31 Select 1 Service Code 35 Enter conductivity values corresponding to output current values.
Appendix 2-13 Sample 3 Concentration of sulfuric acid mixture Meas. range 93-97% Reference temp. 50°C Temp. compensation Enter temperature compensation data into a 5 x 5 matrix START Service code 20 50°C(Default) Service code 31 Select 1 Service code 35 Enter conductivity values corresponding to output current values.
2-14 Appendix Sample 4 Concentration of hydrochloric acid Meas. range 30-40% Reference temp. 35°C Temp. compensation Enter temperature compensation coefficient, Relate concentration to conductivity by table START Service code 20 35 °C (Default) Service code 31 Select 1 Service code 35 Enter conductivity values corresponding to output current values. Table (below) relates output current to conductivity at 35°C Output current (%) 0 20 40 60 80 100 HCl conc.
Appendix 2-15 12-4-3-2 Key Operation Procedure Examples This uses Sample 1 above as the example 1. Reference Temperature Setting Temperature compensation converts the measured conductivity to the equivalent at the reference temperature. The nearer the liquid temperature to the reference temperature, the lower the conversion error. Service code 20 35°C ¼ *OUTP NO *HOLD NO NO *TEMP.2 *SERV NO YES *CODE 20 ENT 35 ENT example1E.
2-16 Appendix 2. Output Table Setting Example *SERV YES *CODE 35 0% ENT YES 845 mS/cm ENT Enter NO 5% NO 20% YES 810 mS/cm 40% ENT Enter NO YES 772 mS/cm 60% Enter NO YES Enter NO 688 mS/cm repeatedly until you reach 80% ENT Enter NO YES 644 mS/cm repeatedly until you reach 60% ENT YES 100% repeatedly until you reach 40% ENT 731 mS/cm 80% repeatedly until you reach 20% repeatedly until you reach 100% ENT example2E.eps 3.
Appendix 2-17 4. Temperature Compensation Coefficient Setting Example ¼ *OUTP NO *HOLD NO *TEMP YES *NaCl NO *TC YES MODE Escape *SERV YES CODE 21 ENT TC 1.24 ENT example4E.eps The temperature compensation coefficient is calculated as follows: α= Kt - Kref T - Tref x 100 Kref T = Measured temperature ( °C ) Kt = Conductivity coefficient at temperature T ( °C ) Tref = Reference temperature ( 25 °C ) Kref = Conductivity coefficient at temperature Tref 5.
2-18 Appendix 6. One-point Calibration example Normally you would do a laboratory analysis when the sensor is installed and use the resulting value to calibrate the transmitter. If the concentration at start-up time is known, then you can use concentration to conductivity tables to determine the conductivity, and use that. For example, suppose that the concentration is known to be 34%, and the transmitter should display the corresponding conductivity which is 772mS/cm: .
Appendix 2-19 12-5. Installation factor adjustment ACCESS CODE : 03 DISPLAY : *C.C. Adjustment: Adjust the ratio between the measured conductance of the sensor and the specific conductivity of the solution. Explanation: The installation factor for the ISC40 detector is the ratio of the measured conductivity of the sensor and the specific conductivity of the solution. This factor varies depending on materials of process piping and the distance between the doughnut sensor and the process piping.
2-20 Appendix IM 12D06A03-01E
Appendix 3-1 13. APPENDIX 3 QUALITY INSPECTION 13-1. ISC202G 2-Wire Inductive Conductivity Transmitter Quality Inspection Standards 1. ISC202G 2-Wire Inductive Conductivity Transmitter Scope This inspection standard applies to the ISC202G 2-Wire Inductive Conductivity Transmitter. 2. Inspection Items 2.1 2.2 2.3 * 2.
3-2 Appendix 2/4 Table 1 3.3 Current Output (Indication) Output Range 4.0 mA 12.0 mA 20.0 mA 4 ±0.02 mA DC 12 ±0.02 mA DC 20 ±0.02 mA DC Temperature Indication Check x From the last step in Item 3.2, Current Output Test, press the [ENT] key repeatedly until the message display shows “PT1000.” x Change the resistance value of the resistance box 1 (for temperature) as shown in Table 2-1 and check the temperature readings. Each temperature reading must be within the range.
Appendix 3-3 3/4 Table 3 SEL.10 Indication RES. 1 RES. 3 RES. 5 x x x x x x x x x x Setpoint of Resistance Box 2 30.00: 800.00: 30.00k: Indication Range 0.300±0.002 8.00±0.04 300±2 Change the number of turns of wire onto the ISC40GJ sensor from ten to one. Press the [ENT] key. The message display shows “ WAIT ” momentarily, followed by “RES.6.” Set resistance box 2 to the value shown in Table 4 and check the indication. The resistance indication must be within the range. Press the [ENT] key.
3-4 Appendix 4/4 ISC202G 11 Resistance Box 1 12 13 ISC40 14 Resistance Box 2 15 16 17 10 turns or 1 turn + + DC Power Source - - Load Resistance 300: + - 24V DC Ammeter G Figure 1 Testing Circuit and Test Equipment QIS 12D06A03-01E IM 12D06A03-01E
Appendix 3-5 IM 12D06A03-01E
3-6 Appendix 13-2. ISC202S 2-Wire Inductive Conductivity Transmitter Quality Inspection Standards 1. ISC202S 2-Wire Inductive Conductivity Transmitter Scope This inspection standard applies to the ISC202S 2-Wire Inductive Conductivity Transmitter. 2. Inspection Items 2.1 * 2.2 2.3 2.4 * 2.
Appendix 3-7 2/4 x x x x When the message display shows “4 mA,” the output current must be within in the range shown in Table 1. Press the [ENT] key repeatedly until the message displays shows “12 mA.” When it shows “12 mA,” the output current must be within the range shown in Table 1. To skip the current output not needed to be checked, just press the [ENT] key. Press the [ENT] key repeatedly until the message displays shows “20 mA.
3-8 Appendix 3/4 x x x x x Press the [ENT] key. The message display shows “ WAIT ” momentarily, followed by “RES.2.” There is no need to check here, so just press the [ENT] key. The message display shows “ WAIT ” momentarily, followed by “RES.3.” Set resistance box 2 to the value shown in Table 3 and check the indication. The resistance indication must be within the range. Press the [ENT] key. The message display shows “ WAIT ” momentarily, followed by “RES.4.
Appendix 3-9 4/4 ISC202S 11 Resistance Box 1 12 13 14 ISC40 Resistance Box 2 15 16 17 10 turns or 1 turn + + DC Power Source - - Load Resistance 300: + - 24V DC Ammeter G Figure 1 Testing Circuit and Test Equipment QIS 12D06A03-21E IM 12D06A03-01E
3-10 Appendix IM 12D06A03-01E
Appendix 3-11 13-3. ISC202G, ISC202S 2-Wire Inductive Conductivity Transmitter (Fieldbus Communication) Quality Inspection Standards 1. ISC202G, ISC202S 2-Wire Inductive Conductivity Transmitter (Fieldbus Communication) Scope This inspection standard applies to the ISC202G and ISC202S 2-Wire Inductive Conductivity Transmitters (Fieldbus specification). 2. Inspection Items 2.1 * 2.2 2.3 * 2.4 * 2.
3-12 Appendix 2/3 In this state, change the resistance value of the decade resistance box 1 as shown in Table 1. The corresponding temperature indication must be within the range. Table 1 Temperature Indication Check (PT1000) Reference Resistance of Temperature Resistance Box 1 25 °C 1097.3 : 100 °C 1385.0 : Indication Range 25.0 ±0.3 °C 100.0 ±0.3 °C Set the type of temperature sensor to 30k NTC. Set Service Code 10 to 0 by following the steps for setting Service Code 10 to 1.
Appendix 3-13 3/3 Figure 1 Testing Circuit and Test Equipment QIS 12D06A03-61E IM 12D06A03-01E
3-14 Appendix IM 12D06A03-01E
Appendix 3-15 13-4. ISC202G, ISC202S 2-Wire Inductive Conductivity Transmitter (Profibus Communication) Quality Inspection Standards 1. ISC202G, ISC202S 2-Wire Inductive Conductivity Transmitter (Profibus Communication) Scope This inspection standard applies to the ISC202G and ISC202S 2-Wire Inductive Conductivity Transmitters (Profibus specification). 2. Inspection Items 2.1 * 2.2 2.3 * 2.4 * 2.
3-16 Appendix 2/3 In this state, change the resistance value of the decade resistance box 1 as shown in Table 1. The corresponding temperature indication must be within the range. Table 1 Temperature Indication Check (PT1000) Reference Resistance of Temperature Resistance Box 1 25 °C 1097.3 : 100 °C 1385.0 : Indication Range 25.0 ±0.3 °C 100.0 ±0.3 °C Set the type of temperature sensor to 30k NTC. Set Service Code 10 to 0 by following the steps for setting Service Code 10 to 1.
Appendix 3-17 3/3 3.5 Profibus Communication Functional Check Check for normal function using Profibus equipment specified by Yokogawa. In the tests of Item 3.3 to 3.4, check the communication function using Profibus communication.
3-18 Appendix IM 12D06A03-01E
Customer Maintenance Parts List Model ISC202G [Style: S2] Inductive Conductivity Transmitter 9 14 8 3 10 11 5 4 6,7 2 Item 1 2 3 4 5 6 7 8 *9 *10 11 12 13 *14 13 12 1 Part No.
2 Pipe/Wall Mounting Hardware (Option Code : /U) 1 1 Panel Mounting Hardware (Option Code : /SCT) 2 Hood to sun protection 3 Option Code : /H /H2 4 (Option Code : /PM) Item 1 2 3 4 CMPL 12D06A03-02E Parts No. K9171SS K9311BT K9311KA K9311KG K9660JA Qty 1 1 1 1 1 Description Universal Mount Set (/U) Tag Plate (/SCT) Fitting Assembly (/PM) Hood Assembly (/H) Hood Assembly (/H2) 2nd Edition : Aug.
Customer Maintenance Parts List Model ISC202S [Style: S3] Inductive Conductivity Transmitter 9 14 8 3 10 11 5 4 6 2 Item 1 2 12 1 Part No.
2 Pipe/Wall Mounting Hardware (Option Code : /U) 1 1 Panel Mounting Hardware (Option Code : /SCT) 2 Hood to sun protection 3 Option Code : /H /H2 4 (Option Code : /PM) Item 1 2 3 4 CMPL 12D06A03-23E Parts No. K9171SS K9311BT K9311KA K9311KG K9660JA Qty 1 1 1 1 1 Description Universal Mount Set (/U) Tag Plate (/SCT) Fitting Assembly (/PM) Hood Assembly (/H) Hood Assembly (/H2) 2nd Edition : Nov.
Revision Record Manual Title : Model ISC202G [Style: S2], ISC202S [Style: S3] 2-wire Inductive Conductivity Transmitter Manual Number : IM 12D06A03-01E Edition Date Remark (s) 1st Sep. 2004 Newly published 2nd Sep. 2005 Revised pages are shown below. PREFACE some corrected (i page); After-sales Warranty modified (iii page). Sec. 2-1. 1. ISC202G Inductive Conductivity Transmitter; Accuracy modified (2-1 page); Transmission range modified (2-1 page); 2.
Edition 6th Date Apr. 2008 Remark (s) Style of ISC202S changed to S3 and related description changed as follows. p2-5, Style of ISC202S changed to S3 for FM approval; p3-1, Some of dimensions in Figure 3-1 corrected; p1-4 (Appendix), Note of HART protrocol DD files URL added; p2-8 (Appendix), NOTE to confirm zero offset after Air Set added to Sec. 12-4-2-4; CMPL 12D06A03-23E 1st edition added for ISC202S style S3. 7th Oct. 2009 PREFACE, "Zone 0" added to Warning label explanation; P.
User’s Manual Model ISC202G [Style: S2], ISC202S [Style: S3] 2-Wire Inductive Conductivity Transmitter Supplement Thank you for selecting our Model ISC202G [Style: S2] and/or ISC202S [Style: S3] 2-Wire Inductive Conductivity Transmitter. User's Manual, IM 12D06A03-01E, 7th Edition, supplied with the product, some revisions/additions have been made. Please replace the corresponding pages in your copy with the attached, revised pages. Revisions: - PREFACE, "How to dispose the batteries" added.
PREFACE Notice • This manual should be passed on to the end user. • The contents of this manual are subject to Electric discharge change without prior notice. The EXA analyzer contains devices that can be • The contents of this manual shall not be damaged by electrostatic discharge. When servicing reproduced or copied, in part or in whole, this equipment, please observe proper procedures without permission. to prevent such damage.
2-2 Specifications Load Resistance (Ω) 800 775 600 425 400 Possible 200 0 12 17 16 20 24 28 32 31.5 V Voltage (V) Fig.2-2 Supply voltage/ load diagram for the ISC202S J) Temperature compensation: - Sensor types: Pt1000Ω or 30kΩ NTC - Automatic: -20 to 140 ºC (0 to 280 ºF) - Algorithm: selectable as mentioned below NaCl according to IEC 60746-3 tables. Two T.C. setting possible between 0.00 to 3.50 %/°C Matrix: user selectable/ configurable.