    <9. Parameter Lists>
9-10
IM 01C25T02-01E
Relative 
Index 
Index 
AI1 
Index 
AI2 
Index 
AI3 
Parameter Name  Factory Default 
Write 
Mode 
Explanation 
3 4003 4103 4203 STRATEGY  1 AUTO  The strategy eld can be used to identify grouping 
of blocks. This data is not checked or processed 
by the block. 
4 4004 4104 4204 ALERT_KEY  1 AUTO  The identication number of the plant unit. This 
information may be used in the host for sorting 
alarms, etc. 
5 4005 4105 4205 MODE_BLK  AUTO  AUTO  The actual, target, permitted, and normal modes 
of the block. 
6 4006 4106 4206 BLOCK_ERR  — — This parameter reects the error status 
associated with the hardware or software 
components associated with a block. It is a bit 
string, so that multiple errors may be shown. 
7 4007 4107 4207 PV  — — Either the primary analog value for use in 
executing the function, or a process value 
associated with it. May also be calculated from 
the READBACK value of an AO block. 
8 4008 4108 4208 OUT  — Value = 
MAN 
The primary analog value calculated as a result of 
executing the function. 
9 4009 4109 4209 SIMULATE  Disable  AUTO  Allows the transducer analog input or output to 
the block to be manually supplied when simulate 
is enabled. When simulation is disabled, the 
simulate value and status track the actual value 
and status. 
10 4010 4110 4210 XD_SCALE  Specied at the 
time of order 
O/S  The high and low scale values, engineering units 
code, and number of digits to the right of the 
decimal point used with the value obtained from 
the transducer for a specied channel. 
11 4011 4111 4211 OUT_ SCALE  Specied at the 
time of order 
O/S  The high and low scale values, engineering units 
code, and number of digits to the right of the 
decimal point to be used in displaying the OUT 
parameter and parameters which have the same 
scaling as OUT. 
12 4012 4112 4212 GRANT_DENY  0 AUTO  Options for controlling access of host computers 
and local control panels to operating, tuning and 
alarm parameters of the block. 
13 4013 4113 4213 IO_OPTS  0 O/S  Options which the user may select to alter input 
and output block processing 
14 4014 4114 4214
STATUS_OPTS  0 O/S  Options which the user may select in the block 
processing of status 
15 4015 4115 4215 CHANNEL  AI1: 1 
AI2: 2 
AI3: 4 
O/S  The number of the logical hardware channel that 
is connected to this I/O block. This information 
denes the transducer to be used going to or from 
the physical world. 
1:PV 
2:SV 
3:TV 
4:CAP_TEMP_VAL 
5:AMP_TEMP_VAL 
6:FLG_TEMP_VAL 
16 4016 4116 4216 L_TYPE  Specied at the 
time of order 
MAN  Determines if the values passed by the 
transducer block to the AI block may be used 
directly (Direct) or if the value is in different units 
and must be converted linearly (Indirect), or with 
square root (Ind Sqr Root), using the input range 
dened by the transducer and the associated 
output range. 
17 4017 4117 4217 LOW_CUT  Linear: 0%  
Square root: 10% 
of OUT_SCALE 
AUTO  Limit used in square root processing. A value of 
zero percent of scale is used in block processing 
if the transducer value falls below this limit. This 
feature may be used to eliminate noise near zero 
for a ow sensor. The setting is in an engineering 
unit of OUT_SCALE.
18 4018 4118 4218 PV_FTIME  0 (s)  AUTO  Time constant of a single exponential lter for the 
PV, in seconds. 
19 4019 4119 4219 FIELD_VAL  — — Raw value of the eld device in percent of thePV 
range, with a status reecting the Transducer 
condition, before signal characterization (L_
TYPE) or ltering (PV_FTIME). 