User Manual

<9. Parameter Lists>
9-9
IM 01C25T02-01E
Relative
Index
Index Parameter Name Factory Default
Write
Mode
Explanation
20 2520 EXP_MODE1 0 O/S Selection of the displayed value in exponent such as x1, x10,
x100, and x1000.
21 2521 BLOCK_TAG2 2014 (PRIMARY_
VALUE)
Block tag which includes a parameter to be displayed on
display2
22 2522 PARAMETER_SEL2 0 (PRIMARY_
VALUE)
O/S Selection of a parameter to be displayed on display2. Select a
parameter from Table 6.1
23 2523 DISPLAY_TAG2 Null O/S Name of block tag to be displayed on display2; up to six
alphanumeric plus a slash [/] and a period [.]
24 2524 UNIT_SEL2 0 (Auto) O/S Selection of unit to be displayed. The unit of the parameter
which is selected at PARAMETER SEL2 will be displayed
when "Auto" is selected; user-specied unit at DISPLAY UNIT2
will be displayed when "Custom" is selected.
25 2525 DISPLAY_UNIT2 Null O/S User specied unit to be displayed on display2, which will be
available when "Custom" is selected at UNIT SEL2.
26 2526 EXP_MODE2 0 O/S Selection of the displayed value in exponent such as x1, x10,
x100, and x1000.
27 2527 BLOCK_TAG3 2029
(SECONDARY_
VALUE)
Block tag which includes a parameter to be displayed on
display3
28 2528 PARAMETER_SEL3 1 (SECONDARY_
VALUE)
O/S Selection of a parameter to be displayed on display3. Select a
parameter from Table 6.1
29 2529 DISPLAY_TAG3 Null O/S Name of block tag to be displayed on display3; up to six
alphanumeric plus a slash [/] and a period [.]
30 2530 UNIT_SEL3 0 (Auto) O/S Selection of unit to be displayed. The unit of the parameter
which is selected at PARAMETER SEL3 will be displayed
when "Auto" is selected; user-specied unit at DISPLAY UNIT3
will be displayed when "Custom" is selected.
31 2531 DISPLAY_UNIT3 Null O/S User specied unit to be displayed on display3, which will be
available when "Custom" is selected at UNIT SEL3.
32 2532 EXP_MODE3 0 O/S Selection of the displayed value in exponent such as x1, x10,
x100, and x1000.
33 2533 BLOCK_TAG4 2047 (CAP_
TEMP_VAL)
Block tag which includes a parameter to be displayed on
display4
34 2034 PARAMETER_SEL4 3 (CAP_TEMP_
VAL)
O/S Selection of a parameter to be displayed on display4. Select a
parameter from Table 6.1
35 2535
DISPLAY_TAG4 Null O/S Name of block tag to be displayed on display4; up to six
alphanumeric plus a slash [/] and a period [.]
36 2536 UNIT_SEL4 0 (Auto) O/S Selection of unit to be displayed. The unit of the parameter
which is selected at PARAMETER SEL4 will be displayed
when "Auto" is selected; user-specied unit at DISPLAY UNIT4
will be displayed when "Custom" is selected.
37 2537 DISPLAY_UNIT4 Null O/S User specied unit to be displayed on display4, which will be
available when "Custom" is selected at UNIT SEL4.
38 2038 EXP_MODE4 0 O/S Selection of the displayed value in exponent such as x1, x10,
x100, and x1000.
39 2039 BAR_GRAPH_
SELECT
1 (display) O/S Selection of bar graph indicator
40 2540 DISPLAY_CYCLE 7 (2.8 s) O/S Duration of display cycle. (Time unit: 1=400 ms)
41 2541 POWER_ON_INFO 1 Display when powering on.
42 2542 TEST 40 0 O/S Not used for the transmitter.
9.4 Al Function Block
Relative
Index
Index
AI1
Index
AI2
Index
AI3
Parameter Name Factory Default
Write
Mode
Explanation
0 4000 4100 4200 Block Header TAG: “AI1” or
“AI2” or
“AI3”
Block
Tag =
O/S
Information on this block such as Block Tag, DD
Revision, Execution Time etc.
1 4001 4101 4201 ST_REV The revision level of the static data associated
with the function block. The revision value will be
incremented each time a static parameter value in
the block is changed.
2 4002 4102 4202 TAG_DESC Null AUTO The user description of the intended application
of the block.