User Manual

<9. Parameter Lists>
9-6
IM 01C25T02-01E
Relative
Index
Index Parameter Name Factory Default
Write
Mode
Explanation
18 2018 CAL_MIN_SPAN Minimum span of
capsule
The minimum calibration span value allowed.
19 2019 CAL_UNIT kPa The engineering unit for the calibrated values.
20 2020 SENSOR_TYPE Silicon resonant The type of sensor.
21 2021 SENSOR_ RANGE Range of capsule The High and Low range limit values, engineering units code
and the number of digits to the right of the decimal point for the
sensor.
22 2022 SENSOR_SN Serial No. Serial number.
23 2023 SENSOR_CAL_
METHOD
103: factory
trim standard
calibration
O/S The method of the last sensor calibration.
100=volumetric
101=static weight
102=dynamic weight
103=factory trim standard calibration
104=user trim standard calibration
105=factory trim special calibration
106=user trim special calibration
255=Other
24 2024 SENSOR_CAL_LOC O/S Set/indicate the location of the last sensor calibration.
25 2025 SENSOR_CAL_DATE O/S Set/indicate the date of the last sensor calibration.
26 2026 SENSOR_CAL_WHO O/S Set/indicate the name of the person responsible for the last
sensor calibration.
27 2027 SENSOR_
ISOLATOR_MTL
Unkown Denes the construction material of the isolating diaphragms.
28 2028 SENSOR_FILL_
FLUID
Unkown Denes the type of uid used in the sensor.
29 2029 SECONDARY_VALUE Static pressure (high pressure side) value and status
30 2030 SECONDARY_
VALUE_UNIT
1133 (KPa) The engineering unit of static pressure (high pressure side).
This unit is linked to XD_SCALE.unit of AI blocks
31 2031 CAL_DEVIATION_HI 0 O/S Deviation value for span adjustment.
32 2032 CAL_DEVIATION_LO 0 O/S Deviation value for zero adjustment.
33 2033 EXTERNAL_ZERO_
TRIM
0 O/S Permission of external zero-adjustment
34 2034 PRIMARY_VALUE_
FTIME
2 O/S Damping time constant for primary value
35 2035 TERTIARY_VALUE
Value and status of static pressure at low side
36 2036 SP_VALUE_TYPE 109 (absolute
pressure)
O/S Select the type of measurement for static pressure, absolute
or gauge
37 2037 SP_VALUE_RANGE Range of capsule High and low range limit values, engineering units, and decimal
point place for static pressure.
38 2038 CAL_SP_ POINT_HI 16 O/S The highest calibrated value for static pressure
39 2039 CAL_SP_ POINT_LO 0 O/S The Lowest calibrated value for static pressure
40 2040 CAL_SP_MIN_ SPAN 1.0 The minimum calibration span allowed for static pressure
41 2041 CAL_SP_UNIT 1133 (KPa) The calibrated engineering unit for static pressure. This unit is
linked to XD_SCALE.unit of AI blocks
42 2042 CAL_SP_
DEVIATION_HI
0 O/S Deviation value for span adjustment of static pressure
43 2043 CAL_SP_
DEVIATION_LO
0 O/S Deviation value for zero adjustment of static pressure
44 2044 SP_VALUE_FTIME 2 O/S Damping time constant for static pressure
45 2045 ATM_PRESS 101.325 O/S Atmosphere pressure value used to obtain gauge pressure
value from absolute pressure.
46 2046 CLEAR_CAL 0 O/S Reset zero and span adjustment to factory calibrated values for
pressure, static pressure, and or all.
47 2047 CAP_TEMP_VAL Measured capsule temperature value and status.
48 2048 CAP_TEMP_RANGE -50.0 to 130.0°C High and low range limit values, engineering units, decimal
point place for capsule temperature.
49 2049 AMP_TEMP_VAL Measured Amplier temperature value and status.
50 2050 AMP_TEMP_ RANGE -50.0 to 95.0°C High and low range limit values, engineering units, decimal
point place for Amplier temperature.
51 2051 MODEL Model code The model code.
52 2052 SPECIAL_ ORDER_
ID
Special order
number
Identication number of special order.
53 2053 MANUFAC_DATE 0 O/S Date of production